Optional accessories, Voltage probes, Current probes and shunts for ac and dc currents – Atec Fluke-1760 User Manual
Page 9
9 Fluke Corporation Fluke 1760 Three-Phase Power Quality Recorder Topas
Optional accessories
FLUKE-1750/CASE – Water tight transit case with rollers for Fluke 1760 and accessories
GPS-TIME SYNC - GPS time synchronization module provides high accuracy time stamp from GPS clock
Voltage probes
Model No.
Type
Range rms
Vnom
Vmax.
contin.
Fast Transient
Range Vp
< 1ms
Intrinsic
error
Operating
voltage
TPS VOLTPROBE 10 V
Voltage probe
10 V
0.1 V to 17 V
10 V
100 V
–
0.15 %
–
TPS VOLTPROBE 100 V
Voltage probe
100 V
1 V to 170 V
100 V
1000 V
6000
0.15 %
600 V CAT IV
TPS VOLTPROBE 400 V
Voltage probe
400 V
4 V to 680 V
400 V
1000 V
6000
0.15 %
600 V CAT IV
TPS VOLTPROBE 750 V
Voltage probe
400 V/750 V
Peak
4 V to 680 V
400 V
1000 V
5 to 750 detects
voltage harmonics
> 50th with fast
transient
0. %
600 V CAT IV
TPS VOLTPROBE 600 V
Voltage probe
600 V
10 V to 1000 V
600 V
1000 V
6000
> 0.1 %
600 V CAT IV
TPS VOLTPROBE 1 KV
Voltage probe
1000 V
10 V to 1700 V
1000 V
000 V
6000
> 0.1 %
600 V CAT IV
Current probes and Shunts for ac and dc currents
Model No.
Type
Measuring range
selectable per
software
Peak
current for
sinusoidal
currents
Intrinsic
error
Frequency
range
Operating
voltage
Phase
error
Jaw opening
TPS FLEX 18
Flexible current
probe
1 A to 100 A
5 A to 500 A
40 A
1350 A
1 %
45 Hz. to
3.0 kHz
300 V CAT IV
0.5 °
45 cm
(18 inch) length
m cable
TPS FLEX 24
Flexible current
probe
A to 00 A
10 A to 1000 A
480 A
700 A
1 %
45 Hz to
3.0 kHz
600 V CAT IV
0.5 °
61 cm
(4 inch) length
m cable
TPS FLEX 36
Flexible current
probe
30 A to 3000 A
60 A to 6000 A
10 kA
19 kA
1 %
45 Hz to
3.0 kHz
300 V CAT IV
0.5 °
91 cm
(36 inch) length
4 m cable
TPS CLAMP
10 A/1 A
Clip-on current
transformer
0.01 A to 1 A
0.1 A to 10 A
3.7 A
37 A
0.5 %
40 Hz to
10 kHz
300 V CAT IV
0.5 °
< 15 mm
(0.6 in) diameter
or
15 mm x 17 mm
(0.6 in x 0.7 in)
bush bars
TPS CLAMP
50 A/5 A
Clip-on current
transformer
0.05 A to 5 A
0.5 A to 50 A
18 A
180 A
0.5 %
40 Hz to
0 kHz
300 V CAT IV
0.5 °
< 15 mm
(0.6 in) diameter
or
15 mm x 17 mm
(0.6 in x 0.7 in)
bush bars
TPS CLAMP
200 A/20 A
Clip-on current
transformer
0. A to 0 A
A to 00 A
74 A
300 A
0.5 %
40 Hz to
10 kHz
300 V CAT IV
0.5 °
< 15 mm
(0.6 in) diameter
or
15 mm x 17 mm
(0.6 in x 0.7 in)
bush bars
TPS SHUNT
20MA
Shunt 0 mA
ac/dc
0 to 55 mA
77.8 mA
I
max
=1.5A
0. %
DC to
3.0 kHz
300 V CAT II
0.1 °
–
TPS SHUNT
5A
Shunt 5 A ac/dc
0 to 10 A
1.9 A
I
max
=10 A
0. %
DC to
3.0 kHz
300 V CAT II
0.1 °
–
Errors in % of measuring range at 3 °C ± °C (74 °F ± °F) for 48 to 65 Hz
Phase angle error at nominal current
I
max
maximum current without time limit (for ac and dc shunts)