Optional accessories

FLUKE-1750/CASE – Water tight transit case with rollers for Fluke 1760 and accessories

GPS-TIME SYNC - GPS time synchronization module provides high accuracy time stamp from GPS clock

Voltage probes

Model No.

Type

Range rms

Vnom

Vmax.

contin.

Fast Transient

Range Vp

< 1ms

Intrinsic

error

Operating

voltage

TPS VOLTPROBE 10 V

Voltage probe

10 V

0.1 V to 17 V

10 V

100 V

0.15 %

TPS VOLTPROBE 100 V

Voltage probe

100 V

1 V to 170 V

100 V

1000 V

6000

0.15 %

600 V CAT IV

TPS VOLTPROBE 400 V

Voltage probe

400 V

4 V to 680 V

400 V

1000 V

6000

0.15 %

600 V CAT IV

TPS VOLTPROBE 750 V

Voltage probe

400 V/750 V

Peak

4 V to 680 V

400 V

1000 V

5 to 750 detects

voltage harmonics

> 50th with fast

transient

0. %

600 V CAT IV

TPS VOLTPROBE 600 V

Voltage probe

600 V

10 V to 1000 V

600 V

1000 V

6000

> 0.1 %

600 V CAT IV

TPS VOLTPROBE 1 KV

Voltage probe

1000 V

10 V to 1700 V

1000 V

000 V

6000

> 0.1 %

600 V CAT IV

Current probes and Shunts for ac and dc currents

Model No.

Type

Measuring range

selectable per

software

Peak

current for

sinusoidal

currents

Intrinsic

error

Frequency

range

Operating

voltage

Phase

error

Jaw opening

TPS FLEX 18

Flexible current

probe

1 A to 100 A

5 A to 500 A

40 A

1350 A

1 %

45 Hz. to

3.0 kHz

300 V CAT IV

0.5 °

45 cm

(18 inch) length

m cable

TPS FLEX 24

Flexible current

probe

A to 00 A

10 A to 1000 A

480 A

700 A

1 %

45 Hz to

3.0 kHz

600 V CAT IV

0.5 °

61 cm

(4 inch) length

m cable

TPS FLEX 36

Flexible current

probe

30 A to 3000 A

60 A to 6000 A

10 kA

19 kA

1 %

45 Hz to

3.0 kHz

300 V CAT IV

0.5 °

91 cm

(36 inch) length

4 m cable

TPS CLAMP

10 A/1 A

Clip-on current

transformer

0.01 A to 1 A

0.1 A to 10 A

3.7 A

37 A

0.5 %

40 Hz to

10 kHz

300 V CAT IV

0.5 °

< 15 mm

(0.6 in) diameter

or

15 mm x 17 mm

(0.6 in x 0.7 in)

bush bars

TPS CLAMP

50 A/5 A

Clip-on current

transformer

0.05 A to 5 A

0.5 A to 50 A

18 A

180 A

0.5 %

40 Hz to

0 kHz

300 V CAT IV

0.5 °

< 15 mm

(0.6 in) diameter

or

15 mm x 17 mm

(0.6 in x 0.7 in)

bush bars

TPS CLAMP

200 A/20 A

Clip-on current

transformer

0. A to 0 A

A to 00 A

74 A

300 A

0.5 %

40 Hz to

10 kHz

300 V CAT IV

0.5 °

< 15 mm

(0.6 in) diameter

or

15 mm x 17 mm

(0.6 in x 0.7 in)

bush bars

TPS SHUNT

20MA

Shunt 0 mA

ac/dc

0 to 55 mA

77.8 mA

I

max

=1.5A

0. %

DC to

3.0 kHz

300 V CAT II

0.1 °

TPS SHUNT

5A

Shunt 5 A ac/dc

0 to 10 A

1.9 A

I

max

=10 A

0. %

DC to

3.0 kHz

300 V CAT II

0.1 °

Errors in % of measuring range at 3 °C ± °C (74 °F ± °F) for 48 to 65 Hz

Phase angle error at nominal current

I

max

maximum current without time limit (for ac and dc shunts)