Atec Fluke-1760 User Manual
Fluke 1760, Technical data, Three-phase power quality recorder topas
Technical Data
Technical Data
•
Fully Class-A compliant: Conduct tests
according to the stringent international IEC
61000-4-30 Class-A standard
•
GPS time synchronization: Correlate data
with events or datasets from other instruments,
with precision
•
Flexible and fully configurable thresholds
and scale factors: Allows user to pinpoint
specific issues by defining the detailed criteria
for detection and recording of disturbances.
•
Highest safety rating in the industry:
600 V CAT IV/1000 V CAT III rated for use at the
service entrance
•
Uninterrupted power supply (40 minutes):
Never miss important events - even record the
beginning and end of interruptions and out-
ages, to help determine the cause
The Fluke 1760 Three-Phase Power Quality Recorder is the
ideal portable instrument for power quality experts. It is fully
compliant to IEC 61000-4-30 Class-A, for advanced power
quality analysis and consistent compliance testing. Designed
for analysis of utility and industrial power distribution systems,
in medium- and low-voltage networks, the Fluke 1760
provides the flexibility to customize thresholds, algorithms,
and measurement selections. It captures the most
comprehensive details on user-selected parameters and
allows for later analysis and reporting.
Fluke 1760
Three-Phase Power Quality Recorder Topas
Class-A compliance for the most
demanding power quality tests
•
10 MHz, 6000 Vpk waveform capture: Get
a detailed picture of even the shortest event
•
2 GB data memory: Enables detailed, simulta-
neous recording of numerous power parameters
for long periods of time
•
Comprehensive software included: Provides
trend diagrams for root cause analysis, statisti-
cal summaries, report writing and real-time data
monitoring in the online mode
•
Plug and play: Allows quick setup with auto-
matic sensor detection; sensors are instrument
powered, eliminating the need for batteries
•
Rugged field design: Insulated housing and
a solid state design with no rotating compo-
nents, enable reliable testing under nearly
any conditions