Eries, Pecifications, Specifications – Atec Elgar-501b User Manual
Page 2: Single phase output power, Model power output input physical comments

Elgar
■
1.800.733.5427
■
858.450.0085
■
Fax 858.458.0267
■
9250 Brown Deer Road, San Diego, CA 92121
■
www.elgar.com
■
email: [email protected]
21
SL
AND
B S
ERIES
S
PECIFICATIONS
SPECIFICATIONS
OUTPUT
Voltage Range: SL Series: 0-65, 0-130,
0-260 VAC; B Series: 0-32, 0-65, 0-130,
0-260 VAC (varies per model). Specific
output range is selected by jumper change
on rear panel. Consult Elgar for other voltage
ranges.
Rated Power Voltage Range: Full rated
VA from 55-65 VAC, 110-130 VAC, or
220-260 VAC over a ±10% input and rated
PF range
SL Series: Continuous duty at 150% of
rated capacity at 55C°*
B Series: Continuous duty at 100% of
rated capacity*
Load Power Factor: Unity to ±0.7 PF at
rated VA with an output voltage
adjustment range of 85-100% of full scale*
Frequency Range: 45 Hz to 5 kHz at full
rated power
Total Harmonic Distortion:
SL Series: 0.4% 200 Hz to 1000 Hz
0.6% Full frequency range
B Series: 0.5% 100 Hz to 1000 Hz
0.9% Full frequency range
Load Regulation: ±1% no load to full
load over full frequency range. Better than
±0.25% for fixed frequency output.
Adjustable to ±0.1% for specific load
conditions and to ±0.015% with a PIP
Line Regulation: ±0.25% at rated load
for a ±10% input change at full scale
output voltage
Response Time: < 50 microseconds
AC Noise Level: 70 dB below full output
voltage with input grounded
INPUT
Voltage SL Series: See model number
description on page 23.
Three Phase B Series Models: See table
Frequency: 47 to 63 Hz (400 Hz option,
special order)
Efficiency: Up to 45%
GENERAL
Operating Temperature Range: 0° to
+55°C
Operating Humidity Range: Up to 95%
non-condensing
Metering: SL Series: 0-300 VAC output
voltmeter, ±3% accuracy
B Series: 0-150 VAC
Controls: Input power switch/circuit
breaker and pilot light. Full range, 10-turn
output voltage control potentiometer
*See Power Rating Curve on page 23.
Single Phase Output Power
Model
Power
Output
Input
Physical
Comments
Total VA
Vol. Range
Max Current
Frequency
Voltage and Nominal/Max
Height and Depth
Weight WT
(RMS)L-N
(RMS)
1
Range (Hz)
Phase
(kVA)
2
(in/mm) (lbs/kg)
121B
120
0-130
1.1
45 to 5k
115 or 230, 1ø
0.4 3.5/89
H
47/21
Net
0-32V/4.4A
range
available;
0-260
0.55 5/127
D
51/23
Ship
Model
121B-101
251B
250
0-32
9.2
45 to 5k
115 or 230, 1ø
0.8 5.25/133
H
49/22
Net
0-130 2.25
16/405
D
55/25
Ship
0-260
1.1
351 SL-XX
350
0-65
8.0
45 to 5k
115 or 230, 1ø
1.0/1.6
5.25/133 H
75/34
Net
0-130
4.0 21/533
D
83/38
Ship
0-260 2.0
501 SL-XX
500
0-65
11.5
45 to 5k
115 or 230, 1ø 1.5/2.2
5.25/133
H 80/36
Net
0-130 5.8
21/533 D
88/40
Ship
0-260 2.9
751 SL-XX
750
0-65
17.3
45 to 5k
115, 208 or
2.2/3.2
7.00/178
H
115/52
Net
0-130 8.65
230,
1ø
21/533
D 25/57
Ship
0-260
4.3
1001 SL-XX
1000
0-65
23.1
45 to 5k
115, 208 or
3.0/4.2
7.00/178
H
125/57
Net
&
0-130 11.5
230,
1ø
21/533 D
135/61
Ship
1001 SLE-2X
0-260 5.8
1001 SLE-21 only
1751 SL-XX
1750
0-65
40.4
45 to 5k
115, 208 or
5.2/7.5
12.25/311
H
190/86
Net
&
0-130 20.2
230,
1ø
21/533
D 200/91
Ship
1751 SLE-2X
0-260 10.1
1751 SLE-21 only
3001
3000
0-65
54.5
45to 3k
208 or 416
9.0
17.5/445
H
315/143
Net
0-130 27.2
L-L,
3
ø
22/560
D 361/164 Ship
0-260 13.6
3500 SL-XX
3500
0-65
80.8
45 to 5k
115, 208
10.5/15.0
24.50/622
H
380/172
Net
2ea 1751 SL, 1 ea 400 SR,
&
0-130
40.4
or 230, 1ø
21/533 D
400/182
Ship
1ea signal
cable
3500 SLE-2X
0-260
20.2
3500 SLE-21 only
6000-1
6000
0-130
54.5
45 to 3k
208 or 416,
18.0
35/890
H
630/286
Net
2ea 3001 (Series)1ea 400 SR
0-260
27.2 L-L,
3ø 22/560
D
722/328
Ship
1ea signal
cable
0-520 13.6
9000-1
9000
0-130
81.8
45 to 3k
208 or 416,
27.0
52.5/1335
H
945/429
Net
3ea 3001-165A (parallel)
0-260 40.9
L-L,
3ø
22/560
D
1083/492
Ship
2ea 400 SR, 1ea signal cable
1
All SL models are specified at 150% of normal output current into a linear resistive load
2
SL models show value in kVA for both nominal and 150% load