beautypg.com

I/ix series : product specifications – Atec California-Instruments-i-iX_SeriesII User Manual

Page 7

background image

858.458.0223

[email protected]

175

i/iX Series : Product Specifications

Harmonic Measurements (iX series)

Parameter

Range

Accuracy (±)

Resolution

Frequency fundamental

16.00 - 1000 Hz

2 counts

0.01 Hz to 1 Hz

Frequency harmonics

32.00 Hz - 16 kHz

2° typ.

0.5°

Voltage

Fundamental

0.25V

0.01V

Harmonic 2 - 50

0.25V + 0.1% + 0.1%/kHz

0.01V

Current

Fundamental

0.05A

0.01A

Harmonic 2 - 50

0.05A + 0.1% + 0.1%/kHz

0.01A

Accuracy specifications are times three for three phase mode. Harmonics frequency range in three-phase mode is 32 Hz - 16 kHz. Resolution decreases by factor
of 10 for 10001iX and 15001iX.

Remote Control

IEEE-488 Interface optional / USB standard IEEE-488 (GPIB) talker listener. Subset: AH1, C0, DC1, DT1, L3, PP0, RL2, SH1, SR1, T6, IEEE-488.2 SCPI Syntax (GPIB standard on iX)

RS232C Interface

(LAN Optional)

9 pin D-shell connector, Handshake: CTS, RTS, Data bits: 7,8, Stop bits: 1, 2, Baud rate: 9600, 19200, 38400, 57600, 115200, IEEE-488.2
SCPI Syntax (Supplied with RS232C cable). (RS232C Standard on iX - LAN Optional)

AC Input

Voltage

3001 and 9003: 208-240 ± 10% Vac, (L-N, 1ø), All other models: Standard: 208-240 ± 10% Vac, (L-L, 3ø), Option -400: 400-480 ± 10%
Vac, (L-L, 3ø) (Input range must be specified when ordering).

Input Line Current (per phase):

Model

3001i/iX

5001i/iX

9003i/iX

10001i/iX

15001i/iX

15003i/iX

187-264V

25 A

23 A

75 A

46 A

69 A

69 A

360-528V

N/A

12 A

N/A

24 A

36 A

36 A

Inrush Current per chassis

< 100 Apk for 100 µs at 208-240 V, < 50 Apk for 100 µs at 400-480 V

Line Frequency

50-60 Hz ± 10 %

Efficiency

75% typical

Power Factor

0.6 typical

Regulatory

IEC61010, EN50081-2, EN50082-2, CE EMC and Safety Mark requirements

RFI Suppression

CISPR 11, Group1 , Class A

Rear Panel Connectors

AC Input & Output terminal block with cover, IEEE-488 (GPIB) connector (rear panel), 9 pin D-Shell RS232C connector*, Remote voltage
sense terminal block, System Interface Connector, *RS232 DB9 to DB9 cable supplied

Mechanical

Dimensions

Height: 7” (178 mm), Width: 19” (483 mm), Depth: 24” (610 mm) (depth includes rear panel connectors)

Weight

per Chassis: Net: 61 lbs / 28 Kg, Shipping: 115 lbs / 52 Kg

Vibration and Shock

Designed to meet NSTA project 1A transportation levels

Air Intake/Exhaust

Forced air cooling, side air intake, rear exhaust.

Operating Humidity

0 to 95 % RAH, non condensing.

Temperature

Operating: 0 to 40° C, Storage: -20 to +85° C

Constant Power AC Mode - Available Max. AC Current

V-F Rating Chart - 300V Range

Note: Specifications are subject to change without notice. Specifications are warranted over an ambient temperature range of 25°± 5° C. Unless otherwise noted,
specifications are per phase for a sinewave with a resistive load and apply after a 30 minute warm-up period. For three phase configurations, all specifications are for L-N.
Phase angle specifications are valid under balanced load conditions only.

3000–15000 VA