beautypg.com

Alpha Technologies EDSM User Manual

Page 19

background image

704-721-C0-004, Rev. D

19

3.0

Module Installation, continued

3.1

XMS2 Communication Module Removal Procedure, continued

19. Press and hold the STAT push-button on the front panel of the EDSM until all LEDs go

out, continue to press the button until the RDY LED is lit indicating that the reset function
is initiated. A reset will force the EDSM to "ping" all devices in the system.

20. Place a magnet over the tamper sensor to override the Tamper Alarm.

21. Verify that the ALM LED is off, and the RDY LED is fl ashing at a 1Hz rate (once per

second). If alarms are present, use the table below to determine the cause and take
corrective action.

22. After all alarms are cleared, verify no alarms are present at the head end.

Problem

Cause

Solution

RDY LED on solid

SW2 Pos 4 'Program' in the
ON position

Set SW2 Pos 4 to the OFF
position

LEDs on and not fl ashing

STAT switch pressed to
indicate alarm codes

Continue pressing STAT until all
LEDs fl ash

LEDs off and not fl ashing

XMS2 (2x9) header missing Insert header

Individual battery readings
not displaying properly

Incorrectly wired batteries

Verify wiring harness is properly
terminated at each battery

Damaged connector/pins

Inspect connector pins, replace
harness if necessary

Table 3-1, Troubleshooting