3.1 XMS2 Communication Module Removal Procedure
Allow 15 minutes for completion of procedure
Tools required: #2 Phillips screwdriver
1. Disconnect any status monitoring cables/harnesses connected to the front panel of the
communications module.
2. Verify that the battery breaker is OFF.
3. Disconnect the battery cable connections.
4. Unscrew the three captive mounting/grounding screws located on the front panel of the
Inverter Module (IM), and on the existing communications module.
5. Slide the IM out of the chassis just far enough to reach the ribbon cable at the back of the
module. See Fig. 3-1.
6. Unlatch the locking clips holding the ribbon cable connector into the plug, and gently
remove the connector from the plug.
3.0 Module Installation
•
If the XMS2 system already has an existing comm module installed, remove the module as outlined in the
procedure below. If the system does not have a communications module installed, proceed to the next
section for the installation procedure.
•
During this procedure, backup capability will be temporarily lost.
Unlatch
Disconnect here
NOTE: