Alpha Technologies CXPS-HD 48-1.2-225 User Manual
Page 41
Specifications for Alpha CXPS-HD 48-1.2-100 and CXPS-HD 48-1.2-225 Standard 48 Vdc Power Systems
Alpha Technologies Ltd.
0530082-S0 Rev B
Printed in Canada. © 2011 Alpha Technologies Ltd. ALPHA and CORDEX are trademarks of Alpha Technologies Ltd. All Rights Reserved. Page
2
of
4
Input
Voltage
Operating: 208/220/240 Vac (nominal)
Operating Range: 90 to 300 Vac (continuous)
90 to 176 Vac (de-rated output power)
Frequency 45
to
66
Hz
Current
7.5 A max (176 to 300 Vac) per module
6.0 A max (90 to 176 Vac) per module
Efficiency
> 93% (50 to 100% load at nominal input voltage)
Power Factor
> 0.99
Recommended Feeder
Single Phase 15 A, 120 Vac, #14 AWG for every two rectifier modules
Breaker
Single Phase 20 A, 208/220/240 Vac, #12 AWG for every two rectifier modules
Electrical Noise
< 38 dBrnC (voice band)
< 10 mV
RMS
10 kHz to 10 MHz (wideband)
< 150 mVp-p 10 kHz to 100 MHz
Environmental
Temperature
-40 to +65°C (-40 to +149°F)
-40 to +75°C (-40 to +167°F) de-rated output
Humidity
0 to 95% RH, non-condensing
Elevation
-500 to +2800 m, to 4000 m with temperature de-rated to 40°C (-1640 to 9186 ft,
to 13124 ft with with temperature de-rated to 104°F) with de-rated output
Miscellaneous
Configurations
System model CXPS-HD 48-1.2-100
0530081-002: 100 A System with Low Voltage Battery Disconnect (LVBD)
0530081-003: 100 A System without LVBD
System model CXPS-HD 48-1.2-225
0530082-002: 225 A System with Low Voltage Battery Disconnect (LVBD)
0530082-003: 225 A System without LVBD
Number of Rectifiers
System model CXPS-HD 48-1.2-100
Up to 4x 48V-1.2 rectifier positions
System model CXPS-HD 48-1.2-225
Up to 9x 48V-1.2 rectifier positions
Distribution
10x load breaker positions (mini breaker, plug-in style)
4x battery breaker positions (mini breaker, plug-in style)
225 A low voltage disconnect option
200 A battery shunt
Controller
CXCM1 Modular controller (included)