Alpha Technologies CXPS-HD 48-1.2-225 User Manual
Page 40
![background image](/manuals/317401/40/background.png)
Specifications for Alpha CXPS-HD 48-1.2-100 and CXPS-HD 48-1.2-225 48Vdc
Power Systems
Alpha Technologies Ltd.
0530082-S0 Rev B
Printed in Canada. © 2011 Alpha Technologies Ltd. ALPHA and CORDEX are trademarks of Alpha Technologies Ltd. All Rights Reserved.
Page 1 of 4
Output
Voltage 48
Vdc
(nominal)
Current
System model CXPS-HD 48-1.2-100:
100 A max @ 48 Vdc (nominal input)
50 A max @ 48 Vdc (115 Vac input)
System model CXPS-HD 48-1.2-225:
225 A max @ 48 Vdc (nominal input)
112.5 A max @ 48 Vdc (115 Vac input)
Rectifier
Module:
25 A max @ 48 Vdc (nominal input)
12.5 A max @ 48 Vdc (115 Vac input)
(subject to de-rating below 110 Vac input)
Power
System model CXPS-HD 48-1.2-100:
4800 W max @ 48 Vdc (nominal input)
2400 W max @ 48 Vdc (115 Vac input)
System model CXPS-HD 48-1.2-225:
10800 W max @ 48 Vdc (nominal input)
5400 W max @ 48 Vdc (115 Vac input)
Rectifier
Module:
1200 W max @ 48 Vdc (nominal input)
600 W max @ 48 Vdc (115 Vac input)
Heat Dissipation
< 308 BTU per hour per rectifier module
Static Load Regulation
Better than ±0.5% for any load change within rated limits
Dynamic Load Regulation
Better than ±2% for 10% to 90% load step
(output shall recover to static limits within 10 ms)
Static Line Regulation
Better than ±0.1% for any change in input voltage within rated limits
Dynamic Line Regulation
Better than ±1% for any change in input voltage within rated limits
(output voltage should recover to static limits within 2 ms)
Electrical Noise
< 38 dBrnC (voice band)
< 30 mVrms 10 kHz to 10 MHz (wideband)
< 150 mVp-p 10 kHz to 100 MHz
< 2.0 mV (psophometric)
Acoustic Noise
< 60 dBa @ 1 m (3 ft.) @ 30°C (86°F)