Peukert number and battery capacity, 1 introduction – Alpha Technologies Micro Secure UPS User Manual
Page 73
71
017-220-J0 Rev B
10. Peukert Number and Battery Capacity
10.1 Introduction
The Alpha Micro Secure series UPS units run on batteries when the AC utility power fails. In this mode, the user
may want to estimate the remaining time that UPS batteries can supply power to the loads.
The battery run time remaining is calculated based on the Peukert equation. Two critical parameters are required
for the equation:
• Peukert number.
• Peukert capacity.
The Peukert number and Peukert capacity depend on the battery characteristics. This document describes the
procedures to determine the Peukert number, and Peukert capacity for the selected battery.
Once the Peukert number and capacity are determined, enter these values in the GUI or web interface. The
Alpha Micro Secure will report the remaining battery run time.
The Peukert equation and the remaining battery run time are estimates only. The actual run time may vary based
on various parameters like the age and status of the batteries etc.
10.2 Determining the Peukert Number and Peukert Capacity
1. Obtain the data sheet of the selected battery.
2. Calculate the nominal load current for the application.
Example: If the load is 150 W and the battery string is 24Vdc, the load current is calculated as 150W / 24V =
6.25A.
3. Find the current discharge ratings table in the data sheet. From the table, pick two current discharge values
(I1 and I2) that are closest to the calculated load current and look up the two discharge hours (R1 and R2).
4. Use the following formula to calculate Peukerts number and capacity:
Peukert’s number = n =
Log (R
2
/R
1
)
(Log (I
1
) - Log (I
2
))
(1)
Peukert’s capacity = (I
1
)
n
x R
1
per battery
(2)
10.3 Determining Peukert Capacity for Series Parallel Combinations
1. For batteries connected in series, the Peukert’s capacity for the battery bank is given by the equation:
Peukert’s capacity
Battery bank
= Peukert’s capacity
per battery
Ah
(as calculated in equation (2))
2. For batteries connected in parallel, the Peukert’s capacity for the battery bank is given by the equation:
Peukert’s capacity
Battery bank
= Peukert’s capacity
per battery
x N Ah
(where N = number of batteries in parallel)