5.3 Wiring the Alpha Micro Secure

5.3.1 Tools and Materials Required

• Slotted-tip screwdrivers for tightening screws on terminal blocks
• DC voltmeter
• Maximum of 12 AWG wire for wiring the input and output terminal blocks
• If used, maximum of 16 AWG wire for wiring the dry contact terminal blocks

Procedure

You may have to connect the dry contact terminal block outputs and the RS-232 connector depending on your

requirements.

1. Connect the load wiring to the output terminal block as labeled. Torque to 7.0 lb-in (0.8 Nm).

2. If used, connect the dry contact terminal blocks and the RS-232 or Ethernet connectors. If using a conduit,

drill a 1/2" hole to attach a matching conduit.

3. Wire the input terminal block according to its label. Torque to 7.0 lb-in (0.8 Nm).

Before starting, make sure line power is turned off and the UPS Input breaker and
battery breakers are OFF.

WARNING!

To Load

Drill hole

to attach

incoming

conduit

1

3

From Line

Power

Input

terminal

block

Dry contact

terminal

block

Output

terminal

block

Figure 6 — Wiring the Alpha Micro Secure