6.2 Communicating with the RS-232 interface
6.2.1 Wiring the RS-232 port
The Alpha Micro Secure’s front panel has a DE-9 female connector. When connected to a PC with Windows
HyperTerminal or other terminal emulation software, the Alpha Micro Secure can be remotely monitored and
controlled with it’s command-line system. The Alpha UPS Monitor provides a Windows or web browser type of
control.
Procedure
1. Connect a 9-pin, fully shielded, straight-through DE-9 to DE-9 connector cable between the computer’s port
and the Alpha Micro Secure’s port.
2. Configure the communications parameters to the values shown in the terminal set up table below.
Figure 9 — RS-232 pin connections
Table C — Terminal Set Up Table
Emulation Type
VT 100 or
Compatible
Backspace
N/A
Duplex Mode
Half Duplex
Break Length
N/A
Xon/Xoff Flow Control
None
Emulation Type
N/A
RTS/CTS Flow Control
Off
Communication Parameters
Line Wrap
On
Handshaking
Software Handshaking
Screen Scroll
On
Baud Rate
2400 bps
CR Translation
CR
Data Format
8-bit Data, No Parity, 1 Stop Bit, No Flow Control.