5 Maintenance

64

Alpha Technologies

5.4 Replacing the Internal Batteries (Continued)

Step 2: Charger Voltage Test

This tests the unit’s charger so the new batteries will not damaged by a faulty charger. Do
this before removing the batteries.

Procedure:

1

Make sure:

• The Battery circuit breaker is switched off.

• The Input circuit breaker is switched on.

• The utility line is connected.

2

Measure the DC voltage by:

3

The voltage should be between 54 VDC to 57 VDC.

• If it is, switch off the Input circuit breaker and disconnect the utility line.

If it is not, the charger is faulty. Contact Alpha Technologies customer service de-

partment.

Charger Voltage Test Finished. Go to Step 3.

Figure 5.2

Charger Voltage Test

TO BATTERIES

RE
L

A

Y

TERM

IN

AL
BLOC

K

RED WIRES

1) CONNECT POSITIVE (+) TO EITHER RED WIRE TERMINAL.
2) CONNECT NEGATIVE (-) TO THE UPS’S CHASSIS.
3) IF VOLTAGE IS BETWEEN 54 AND 57VDC, THE BATTERY

CHARGER IS OK.

IF IT ISN’T, CONTACT ALPHA TECHNOLOGIES CUSTOMER

SERVICE DEPARTMENT.