6. MAINTENANCE

56

Figure 20

Standard Interface Device (Troubleshooting)

SERVICE LED

OUTPUT LOAD LED's

ALARM OFF Switch

Standard Interface Device - Fault Indicators

6.7

Troubleshooting Using the SID

LED

Status

Condition

OVERLOAD

Flashing

Not Applicable

OVERLOAD

ON

Fast Detector / Low Sensitivity Fault

100%

Flashing

PLL Fault

100%

ON

High Ambient Temperature

75%

Flashing

Output Voltage High

75%

ON

Output Voltage Short Circuit

50%

Flashing

PWR BRD Fault / -5 VDC Failure

50%

ON

PWR BRD EPROM Failure

25%

Flashing

Self-Test Failure

25%

ON

Battery Over-Voltage / Charger Fault

The OUTPUT LOAD LED’s, located on the front panel of the Standard

Interface Device, are designed to display UPS fault conditions once the unit
has detected an internal problem, indicated by the SERVICE LED. This
information provided by the LED’s is extremely useful during troubleshooting
and maintenance. If the UPS is equipped with an I

2

D, refer to its operator’s

manual for further troubleshooting information.

If your UPS SERVICE LED is ON, press and hold the ALARM OFF

switch for approximately 3 seconds. The OUTPUT LOAD LED's indicate: