2. FEATURES

LAN Interface Connector

The Alpha UPS provides a LAN interface port on a DE-9 female

connector. This port may be used to monitor the status of the UPS and
shutdown the output using basic UPS monitoring and shutdown software.

Two dry contacts are provided to indicate LINE FAIL and LOW

BATTERY status information. The port also accepts a dry contact input or
an RS-232 level input to shutdown the UPS output. The shutdown delay,
duration, and recovery modes can be configured using the RS-232 ASCII
terminal commands (see section 5 “RS-232 Terminal Communication”).
This port has the following pin out:

2.5 Communication / Interface Options,

continued

13

Pin out: (DE-9 connector, Female)

Using basic UPS monitoring software you can monitor and shutdown

the CFR through this port. In network applications, your UPS monitoring
software can perform an orderly shutdown on the network. Basic UPS
monitoring software is provided as part of many operating systems and can
also be purchased from third party vendors. Alpha Technologies “AlphaNet
C shutdown software” can also operate in the basic mode to shutdown the
CFR before its battery reserve is exhausted. Refer to

AlphaNet C Shutdown

Software User’s Manual or contact Alpha Technologies for more information.