beautypg.com

3 battery testing, Maintenance – Alpha Technologies CFR 600, CFR 600XT, CFR 1000 User Manual

Page 55

background image

6.3 Battery Testing

To determine the maximum amount of battery run time available, run this

test at least once a year. The length of the test can vary from several minutes
to many hours and should not be done during critical applications. Since the
test discharges the batteries, backup power may not be readily available (for
several hours) in the event of a utility power failure.

1. Unplug the AC Line cord from the wall receptacle. The front panel “LINE

FAILURE” LED will come ON. Make a note of the START time.

2. When the CFR reaches LOW BATTERY WARNING, record the time.

Subtract the START time to determine the actual safe run time. To cancel
the test, plug the AC Line cord back into the wall receptacle.

3. To determine the reserve time available, allow the UPS to continue until it

reaches LOW BATTERY SHUTDOWN. Warning: This will cause the
load to go down. Make a note of the time. Subtract the LOW BATTERY
WARNING time to determine your available reserve time.

4. Switch the load OFF. Plug the AC Line cord back into the wall receptacle.

The “LOW BATTERY WARNING” LED will remain ON until the batteries
are partially recharged. Switch the load ON, one device at a time. To
determine recharge time, subtract the time you resumed LINE PRESENT
operation from when the “LOW BATTERY WARNING” LED goes OFF.

6. MAINTENANCE

Figure 15 -Intelligent Interface Device

49

ALPHA TECHNOLOGIES

05-07-92 08:02:10

LINE PRESENT

LINE FAILURE

LOW BATTERY

WARNING

SHUTDOWN

SERVICE

Figure 14 - Standard Interface Device