5. RS-232 TERMINAL COMMUNICATION
5.11 Parameter Dump Command (Function 0)
Parameter Dump Command (Function 0)
Function ‘0’ displays all UPS parameters in the following format:
#####,###.#,#####,#####,##.##,###.#,#####,###.#,#####,###.#,#####,#####,##.##,
###.#,###.#,###.#,xxxxx,#####,#####,#####,#,##,##,##,##,##,##,##,##,
###############,############
Where ‘#’ indicates a digit or a blank character and ‘x’ represents a
letter. The string is terminated by a Carriage Return and a Line Feed.
Parameters are separated by a comma (‘,’). Above is the exact format for
the SID option; IID option has slightly different format (less blank charac-
ters). This command lists the CFR parameters in the following order:
1. Input Voltage
17. Charger Status
2. Input Current
18. Battery Temperature
3. Input VA
19. Efficiency
4. Input Watts
20. Capacity
5. Input Power Factor
21. Run Time Remaining
6. Input Frequency
22. Mode Data
7. Output Voltage #1
23. Input Alarms #1
8. Output Current #1
24. Input Alarms #2
9. Output Voltage #2
25. Battery Alarms
10. Output Current #2
26. Output Alarms
11. Output Watts
27. Environmental Alarms
12. Output VA
28. Inverter Alarms
13. Output Power Factor
29. System Alarms
14. Output Frequency
30. IID/Micro Board Serial #
15. Battery Voltage
31. Unit model - config. version
16. Battery Current
Example:
114, 1.22, 133, 38, 0.29, 59.9, 127, 0.31, 222, 0.49, 95, 0, 0.00,
59.9, 55.2, 2.8,ON , 24, 0, 0, 0,00,00,00,00,00,00,00,00,
88430A000000CA,001060001000
0
42
In the above example, 114 represents the Input Voltage, 1.22 repre-
sents the Input Current, 133 represents the Input VA, etc.