12 event descriptions – Alpha Technologies CFR 600, CFR 600XT, CFR 1000 User Manual
Page 49
5. RS-232 TERMINAL COMMUNICATION
5.12 Event Descriptions (Alarms)
43
There are 6 alarm groups which upon activation will be displayed at the end
of the opening menu. These are:
INPUT:
BATTERY:
OUTPUT:
ENVIRONMENTAL:
SERVICE1:
SERVICE2:
The following lists the mnemonics and description for each alarm group:
INPUT:
FREQ_LO
- input line frequency low
FREQ_HI
- input line frequency high
GLITCH
- input line glitch has been detected
SPIKE
- input line spike has been detected
SAG
- input line sag has been detected
SURGE
- input line surge has been detected
BROWNOUT
- input line brownout has been detected
SLOW_SURGE
- input line slow surge has been detected
BLACKOUT
- input line blackout has been detected
BATTERY:
LO_BAT_SHTDWN - battery voltage shutdown level detected
LO_BAT_WARN
- battery voltage low warning level detected
BAT_VOLT_HI
- battery over voltage level detected *
FAIL_SELF_TEST
- failed self test *
BATT_FLT
- battery fault has been detected *
OUTPUT:
VOLT_LO
- output voltage low has been detected
VOLT_HI
- output voltage high has been detected
PWR_OVLD
- output power overload has been detected
VA_OVLD
- output VA overload has been detected
OVER_V_FLT
- output over voltage fault has been detected *
SHORT_CCT
- output short circuit has been detected *
ENVIRONMENTAL:
AMB_TEMP_HI
- high internal ambient temperature detected *
SERVICE 1:
SERV CODE 1
- phase lock loop failure has been detected *
SERVICE 2:
SERV CODE 2
- micro software reset has been activated
SERV CODE 3
- micro hardware reset has been activated
SERV CODE 4
- power board EEPROM fault has been detected *
SERV CODE 5
- power board hardware fault has been detected *
SERV CODE 6
- neg DC supply rail has been detected *
EMGNCY POFF
- emergency power off has been activated
OUTV SHTDWN
- remote shutdown feature is currently active
*(service light alarm)