2 filter cleaning, ce-3x2 5k-t – Alpha Technologies AlphaGen PN-6x-T 7.5kW 48VDC - Technical Manual User Manual
Page 77
042-288-B0-001, Rev. A
77
Fig. 7-1, Captive Fastener Location, CE-3x2 5K-T
7.0 Maintenance,
continued
7.2 Filter Cleaning, CE-3x2 5K-T
The air intake fi lter (Alpha P/N 561-216-10) is located on the rear door of the enclosure.
Failure to keep the fi lter clean, or using improperly installed fi lters, may cause system failure due
to dirt buildup or lack of cooling air. Equipment failures caused by fi lter blockage, incorrect fi lter
substitution, or dirt ingress due to clogged or improperly installed fi lters are not covered under
warranty.
CAUTION!
Filter Removal, Replacement, and Cleaning
1. Unlock and remove the rear door.
2. Pull the four captive fasteners out, Fig. 7-1.
3. Tilt
the
fi lter frame away from the door and remove the fi lter, Fig. 7-2.
4. Clean
the
fi lter using a vacuum or compressed air (if available) to remove loose dust and
dirt. Then use a soap and water solution to remove any trapped dirt. Use compressed
air to dry the fi lter. After cleaning, re-coat the fi lters using RP Super Filter Coat Adhesive,
available from local suppliers.
5. Replace the fi lter (Verify the “Air Flow” indicating mark faces into the enclosure) and
refasten the fi lter frame.
6. Replace and lock the rear door.
Fig. 7-2, Air Filter Removal, CE-3x2 5K-T