7.0 Maintenance
The engine/alternator requires maintenance at regular intervals to remain reliable and ready to
provide backup power when needed. Please refer to the following table for general maintenance
guidelines. For specifi c recommendations regarding maintenance intervals, please refer to the
supplied engine manufacturer’s operator’s manual.
Maintenance Procedures: X = Action, R = Replace as necessary
Frequency: D = Daily, W = Weekly, M = Monthly, Q = Quarterly, AS = Attended Startup, S = Six Months
Y = Yearly (all numbers in hours)
Table 7-1, Scheduled Maintenance
System Component or
Procedure
Visual Inspection
Verify
Change
Clean
Test
Frequency
FUEL
Inspect flexible lines and
connections
X
R
Q
Check fuel supply
X
W or AS
Inspect fuel piping
X
Y
LUBRICATION
Check oil level
X
X
D, AS
Change oil
R
Y or 100
Replace oil filter
R
Y or 100
COOLING
Verify air ducts, filters, and
free from debris
X
X
Y or AS
EXHAUST SYSTEM
Check for leakage. carbon or
soot residue indicates leaks.
Repair immediately.
X
X
X
Y
Check for fire hazards
X
Y
Check for loose or broken
hangers and supports.
Clean exhaust outlet
X
R
Y or AS
BATTERY CONNECTIONS
Check battery charger
operation, charge rate
X
M
Clean, re-torque battery
terminals
X
X
X
Y or 100
ELECTRICAL SYSTEM
General inspection
X
Q
Inspect cables for abrasion
(Generator compartment)
X
X
S
Reapply corrosion-inhibiting
coating on all exposed
connector assemblies
X
Y
ENGINE & MOUNTING
General insp ection
X
W
Inspect air cleaner element
R
Y or 100
Inspect spark plugs
R
Y or 500
CONTROL SYSTEM
Verify remote control operation
X
M
Run generator set
X
W
GENERATOR SET
Inspect generator set
X
Prestart
Exercise generator set
X
M
GENERAL CONDITION OF
EQUIPMENT
Check for signs of damage due
to vibration, leakage,
excessive noise, extreme
temperature, or deterioration.
X
X
X
W
Inspect and clean cabinet
interior
X
X
Q or AS
Maintenance Procedures