25

021-514-B2-001, Rev. A

5.0 Operation

5.1 Start-up

1. Verify the input voltage select switch on the power module is set for the correct input

voltage. The factory default setting is 230Vac.

LED Color

State

Indication

Green

Solid

Output OK

Green

Blinking

Standby Operation

Red

Blinking

Battery Low/Missing

Red

Solid

Replace Battery

Red & Green

Blinking

Overload (takes precedence)

Table 5-1, Status LED Indications

2. Verify customer-end connections and apply AC power to the unit.

3. Connect the battery terminal left unplugged in Section 4.8.

5.2 Normal

Operation

The green status LED should be ON solid after the battery connection is made. If any other
indication is present, see Section 6.0

for troubleshooting. Operating status of the MPS48-12M

is indicated by two status LEDs located on the power module. Refer to Table 5-1 to determine
operational status and possible faults.

WARNING!

Incorrect voltage selection can damage the unit and void the warranty. Verify the input
voltage select switch matches applied AC input power. Never apply 230Vac to a unit with
the input voltage select switch in the 115Vac position.

Fig. 5-1, Status LEDs

Status LEDs