SQP, SQDLW, SQPH, SQDLWH, SQTH, SQDLWTH, SQDLV, SQDMRH Mounting Frame Installation Instructions

ACCESSING JUNCTION BOX FROM BELOW
To gain access to junction box from below ceiling.

1. Remove trim.

2. Remove lamp. (PAR lamps only)

3. Loosen thumb screw to remove door from
housing and set aside. (see Figure 6).

POST INSTALLATION HOUSING ALIGNMENT
In the event that the trim is in need of alignment
after installation, adjustments can be made to the
housing.

1. Remove trim by gripping edge of flange and
pulling it out of housing.

2. To adjust housing for trim alignment, reach
through aperture and loosen two speed nuts (see
Figure 7). Adjust housing as required and retighten
nuts.

3. Reinstall trim. If needed, refer to trim installation
instructions.

WALLWASH HOUSING ORIENTATION

WALLWASH HOUSING ONLY:
(SQDLW, SQDLWH, SQDLWTH, SQDLV
wallwash and SQDMRH wallwash)

1. Install wallwash housing so that lamp is aimed
away from the wall (see Figure 8). If housing is
installed incorrectly with lamp aimed towards wall,
reach through aperture and remove two (2) speed
nuts. Rotate socket mounting bracket so that it is
aimed away from wall and reinstall speed nuts.

NEW INSTALLATION FOR SQ SERIES
Non-accessible ceiling
(plaster, drywall, etc.):
1. For microflange (MFLG) installation, an
additional component (shipped separately) is
required to be installed PRIOR TO drywall
installation and vertical alignment of this
fixture.
2. Release clamping latch arms and adjust channel
bars to the correct spacing between joists (see
Figure 1).

Mounting Channel Bar-Flexible Wiring Method
3. Bend ends of channel bars 90° and adjustment at
its lowest point on the mounting frame. Make sure
bottom of the flange is flush with the bottom of the
joists. Secure mounting frame into position by
closing the clamping latch arm. Channel bars will
accommodate up to 24” O.C. joists. The notch
located in the draw-down flange of the housing can
be used to assist with alignment of multiple fixtures.

Non-Flexible Wiring Method
If non-flexible wiring methods are used, follow
procedure for Flexible Wiring Method, then lower
mounting frame equal to the thickness of the
finished ceiling or slightly above, (1/8” max. - see
Figure 3). The notch located in the draw-down
flange of the housing can be used to assist with
alignment of multiple fixtures.

4. Remove knockouts on junction box to feed power
supply to fixture (see Figure 5). Supply wire must
meet applicable electrical codes and be rated for a
minimum of 90°C. Junction box is thru-wire rated
for 8-No. 12 AWG conductors(4in- 4out).

Figure 6

Thumb screw

Speed nuts

Figure 7

Figure 8

CJ5200903 Rev. B

6/10 2 of 2