beautypg.com

Bell & Gossett V57050B SRS Pneumatic Purge Valve User Manual

Srs pneumatic purge valve, Instruction manual

background image

SRS

Pneumatic

Purge Valve

SAFETY

INSTRUCTIONS

This safety alert symbol will be used in this manual to draw

attention to safety related instructions. When used, the safety

alert symbol means ATTENTION! BECOME ALERT! YOUR

SAFETY IS INVOLVED! FAILURE TO FOLLOW THESE IN-

STRUCTIONS MAY RESULT IN A SAFETY HAZARD.

DESCRIPTION

The SRS Pneumatic Purge Valve is an air-operated diaphragm

valve with programmable timer. It is used to purge sediment

from an open or closed loop hydronic system that is sepa-

rated out and collected in the bottom of the SRS.

OPERATIONAL LIMITS

Maximum Fluid Operating Temperature: 250°F (121°C)
Maximum Fluid Operating Pressure: 150 PSI (1034 kPa)
Min/Max Ambient Temperature: 32-130°F (0-54°C)
Min/Max Control Air Pressure: 65-145 PSI (450-1000 kPa)

INSTALLATION INSTRUCTIONS

Connections Required To Valve/Timer:

120V AC (±10%) to timer 3-terminal strip.

Air connection to 1/4" FNPT port on solenoid

Valve. 1" FNPT inlet and outlet.
1. Reference Sediment Removal Separator Instruction Manual

A05767.

2. For best results, purge valve/timer should be installed up-

stream of any pipe bends.

3. The purge valve/timer can be installed in any orientation.
4. A manual gate or ball valve is recommended between the

SRS and the purge valve/timer in the event that the purge

valve needs repair. During normal operation, this manual

valve must remain fully open.

CAUTION: The use of PTFE impregnated pipe com-

pound and PTFE tape on pipe threads provides

lubricity which can lead to overtightening and breakage.

Do not overtighten. Failure to follow this instruction can

result in MODERATE personal injury from hot water and/or

property damage.

WARNING LABEL PART NO. V56845

INSTALLED IN THIS LOCATION.

IF MISSING, IT MUST BE REPLACED.

INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.

Figure 1

INLET

FROM BOILER

CHILLER OR

CONVERTER

AUTOMATIC

AIR VENT

B&G SEDIMENT

REMOVAL

SEPARATOR

MANUAL

SHUTOFF

VALVE

BLOW DOWN

VALVE

TO PUMP

SECTION

OUTLET

INSTRUCTION MANUAL

V57050B