beautypg.com

Bell & Gossett A07257B Isolation Flanges User Manual

Isolation flange, Instruction manual, Description

background image

INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.

Isolation

Flange

SAFETY

INSTRUCTION

This safety alert symbol will be used in this manual to draw attention to

safety related instructions. When used, the safety alert symbol means

ATTENTION! BECOME ALERT! YOUR SAFETY IS INVOLVED! FAIL-

URE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN A

SAFETY HAZARD.

DESCRIPTION

The Isolation Flange (IF) is a combination of an isolation valve and a

companion flange for circulators. The isolation flange allows easy serv-

ice or replacement of the circulator without the need to drain the sys-

tem.

INSTALLATION INSTRUCTIONS

1. Install one IF on the suction side of the hydronic circulator and one on

the discharge side.

2. See the following installation instructions and drawings for additional

information.

3. Apply torque in even increments to both flange bolts. Refer to the

pump manufacturers instruction manual for torque value. Both the

suction and discharge flanges must be torqued in this manner.

For NPT connections:

a) Apply pipe compound conservatively to the male connecting fittings

only.

b) Upon completion of IF installation to piping, check connections for

leaks.

For Sweat Connections:

a) For soldering, use 95-5 (Tin-Antimony) solder and a good grade of

flux. Solder end valves are suitable for soldering without disassem-

bly. Refer to table 1 for solder types and temperatures. Solder joint

strength and working pressure varies with tube size, solder grade

and temperature as defined in ASME B16.18 and B16.22. Do not

exceed the limits stated in table 1.

b) Cut the tube square and deburr both ID and OD. Do not deform the

tube, otherwise it must be re-sized. Clean tube end and valve solder

cup with abrasive cloth or wire brush until the surfaces are bright

metal. Alternatively use an approved cleaning paste: in this case

spread the paste evenly on the tube; insert the tube into the cup and

turn to distribute the paste; finally remove the excess paste.

c) When sweating joints, first wrap the valve body with a cool wet rag,

then direct the flame with care to avoid subjecting the valve to ex-

cessive heat. Allow the valve to cool before touching or operating.

The valve must be in the fully closed position during soldering. Valve

seats may be damaged if soldering is done in the open or partly open

position.

WARNING: Wetted surface contains not more than 0.25%

of lead by weight.

WARNING: California Proposition 65 Warning! This product

contains chemicals known to the State of California to cause

cancer and birth defects or other reproductive harm.

Max Temperature 200°F (93°C)
Max Pressure 150psig (10 Bar)

Operational Limits

WARNING: System fluids under temperature or pressure

can be hazardous. Be sure the pressure is relieved and

system temperature is below 100°F (38°C). Failure to follow these in-

structions could result in property damage and/or personal injury.

WARNING: To prevent leakage, make certain that the flange

bolts have been adequately torqued. Failure to follow these

instructions could result in personal injury and/or property damage.

CAUTION: Over-tightening and breakage can occur with the

use of teflon pipe joint compounds. Teflon provides lubricity

so that care must be exercised not to over-tighten joints. Failure

to follow these instructions could result in property damage and/or

personal injury.

NPT

CONNECTION

SWEAT

CONNECTION

INSTRUCTION MANUAL

A07257B