OPERATIONAL LIMITS
WORKING PRESSURE & TEMPERATURE LIMITS
(SOLDER TYPE LIMITS FOR ANSI STD. B.16.18)
NPT
Maximum Operating Pressure 400 psig (2758 kPa)
Maximum Operating Temperature 250°F (121°C)
DESCRIPTION
The Bell & Gossett Tank Purge Valve (TPV) is a combination full port
ball type isolation valve and drain valve used to connect the system to
the expansion tank. This valve allows the tank to be drained for easy
servicing or tank replacement without having to drain the system.
These valves are furnished standard with a drain valve with standard
5
/
8
" hose connection.
MAXIMUM
MAXIMUM
LIMITATIONS
LIMITATIONS
TYPE OF
1
/
2
" – 1"
1
1
/
4
" – 2"
SOLDER
PRESSURE
TEMP
PRESSURE
TEMP
PSI (kPa)
°F (°C)
PSI (kPa)
°F (°C)
95-5
300 (2069)
200 (93)
300 (2069)
175 (79)
TIN-
250 (1724) 225 (107)
250 (1724)
200 (93)
ANTIMONY
200 (1379) 250 (121)
175 (1207)
250 (121)
ISOLATION VALVE
SYSTEM
DRAIN VALVE
TANK
FIGURE 1
WARNING: Damage to the Tank Purge Valve or failure of
solder sealing joints may occur if these operational limits are
exceeded. This can result in water leakage. Failure to follow this in-
struction can cause serious personal injury and/or property damage.
WARNING: Isolation valve must be in the open position with
the handle inline with the valve body when the system is in
operation. Failure to follow these instructions may cause system to
over pressurize and can result in serious personal injury, death and
property damage.
WARNING: Drain valve must be in the closed position
with the handle perpendicular to the valve body when the
system is in operation. Failure to follow these instructions can
cause property damage due to leakage through the drain valve.
NOTE: This product is not intended for use in potable water applications.