Bell & Gossett HS 902D Model 62 Vacuum Breaker User Manual

Hoffman specialty, Model 62 vacuum breaker, Caution

background image

INSTRUCTION MANUAL

HS-902

REVISION D

Hoffman Specialty

®

Model 62

Vacuum Breaker

• Before using this product read and understand instructions.

• Save these instructions for future reference.

• Turn off steam or water before servicing.

• To prevent serious burns, wear heat resistant gloves when handling hot equipment.

Failure to follow this caution could result in property damage or personal injury.

!

CAUTION

OPERATION

As system pressure falls sufficiently below atmospheric pressure to

compress the spring, the vacuum breaker will open, allowing air to

enter the system. The vacuum breaker is factory set to open at

approximately 2 inches Hg vacuum. It is adjustable from 1/4” to 20”

(8 - 508 mm) Hg vacuum.