Bell & Gossett 70M Multiple Pump & Control Pressure Booster Systems User Manual

Page 11

background image

11

37

Low Suct. Auto RST Yes
To change the Low Suction reset, use UP/DOWN key

Yes

Y/N

to enter yes or no

38

System Press. Span 300
Enter value equal to system pressure span

300

0 - 999

39

High Sys. Press. 125
Enter value of the high system pressure above

125

0 - SPAN

which an alarm will be set

40

High Sys. PR. TMR. 20
Enter in seconds (0 - 60) value of proof timer,

20

0 - 60

‘0’ disables this function

41

Audible Alarm 0
Enter 1 for low suction only, 2 for high system only, 3 for

0

0 - 3

low suction and high system, 0 to disable audible alarm

42

Low Sys. Press. 0
Enter value of low system pressure below

0

0 - Span

which an alarm will be set

43

Low Sys. Pr. Tmr. 0
Enter in seconds (0 - 60) value of proof timer,

0

0 - 60

‘0’ disables this function

44

High Temp Cut Out 125
Enter value of the high temp cut-out in deg. F above

125

0 - 200

which an alarm will be set

45

High Temp PR. TMR. 20
Enter in seconds (0 - 60) value of proof timer,

20

0 - 60

‘0’ disables this function

46

High Temp. Reset 100
Enter value of the high temp. Reset in deg. F

100

0 - 199

47

FS NFSD PR TMR
Enter in seconds (5 - 60) value of the

0

5-60

no flow condition proof timer, ‘0’ disables the function

48

NFSD Temp. Cut Out 0
Enter NFSD temp differential, ‘0’ disables this function

5

0-10

49

NFSD Min. Run TMR. 10
Time period (minutes) to ignore no flow sequence

10

0 - 999

after restart from no flow shut down

50

NFSD Restart PSI 0
Enter value of system pressure to restart

0

0 - SPAN

51

NFSD Test Pr. TMR. 0
Enter in seconds (0 - 999), value of the no flow condition

0

0 - 999

proof timer ‘0’ disables this function

52

DP 1 Start Time 30
Time period in seconds to allow pump 1 to start prior

30

15-60

to detecting pump failure

53

DP2 Start Time 30
Time period in seconds to allow pump 2 to start prior

30

15-60

to detecting pump failure

54

DP3 Start Time 30
Time period in seconds to allow pump 3 to start prior to

30

15-60

detecting pump failure

55

DP 1 Proof Time 3
Pump #1 failure proof time in seconds

3

0-30

56

DP 2 Proof Time 3
Pump #2 failure proof time in seconds

3

0-30

57

DP 3 Proof Time 3
Pump #3 failure proof time in seconds

3

0-30

58

Minimum Run Timer 5
Minimum time a pump will run after auto start in minutes

5

0-25

59

Backup Staging

WATTS, AMPS,

Select method of backup staging in the event

WATTS

PSI, GPM,

the primary method fails

TEMP