Display values and adjustments – Bell & Gossett P86272B VS Variable Speed Pump Control User Manual

Page 8

background image

8

These are sensor readings. They can not be adjusted.

◆◆

The display of each setting will remain active for approximately 20 seconds after the last adjustment. Then the display will revert to the default reading.

◆◆◆ These options are available with Reset Mode only. Select r from Startup menu.
◆◆◆◆ These options are available with Return Sensor Mode only. Select rS from Startup menu.

DISPLAY VALUES and ADJUSTMENTS

Press SELECT

DISPLAY

Press and hold either the UP or DOWN button to adjust

Button

Once

OUt

This is the temperature of the outdoor sensor. If it does not read correctly, check the

Outdoor Temp ◆

Troubleshooting guide.

This is the temperature of the water returning to the boiler. If this sensor is not installed

Twice ◆◆◆◆

ret

it will display OPn. If the sensor is installed and does not read correctly, check the

Return Temp ◆

Troubleshooting guide. Available only when the Return Sensor (rS ) is selected from the
Startup menu.

SP

This is the Set Point the Secondary Loop is to maintain. Available only when the Set

3 Times

Set Point

Point (S ) is selected from the Startup menu. It is adjustable from 100° to 180°F with
a default value of 120°F.

3 Times ◆◆◆

CAL

This is the Set Point temperature calculated using the Outdoor Reset logic. Available

Calculated Temp ◆

only when Reset (r ) is selected from the Startup menu.

COF

This is the outdoor temperature below which the VS will activate the Secondary loop

Outdoor Cutoff

pump and control the variable speed pump. If the ON setting is selected, the VS will

4 Times

(warm weather)

activate or control both pumps regardless of outdoor temperature. If the OFF setting is

shut down)

selected, the VS will never activate either pump. It is adjustable from 40° to 100°F with
a default value of 60°F.

The higher the curve number selected, the faster the temperature of the Secondary loop

5 Times ◆◆◆

rSt

will be increased as outdoor temperature decreases. Available only when Reset (r ) is

Reset Ratio

selected from the Startup menu. (For Reset Curves see Figure 6.) It is adjustable from
1 to 12 with a default value of 7.

OFS

The Offset will adjust the calculated Secondary loop temperature (determined by the

6 Times ◆◆◆

Offset

outdoor temperature, Reset Ratio and Setback) by the amount displayed. Available only
when Reset (r ) is selected from the Startup menu. Adjustable ±40°F.

This is the number of degrees the Secondary loop water temperature will be lowered if

7 Times

Sbc

the VC is put into Setback. In addition, this amount will be added to the Secondary loop

Setback

water temperature when control is in Boost (switching from Setback to normal operation)
for a full hour. It is adjustable from 0 to 30 with a default value of 10.

GAn

The Gain controls how aggressively the VS will change the pump speed when the

8 Times

Gain

Secondary loop temperature is away from the Calculated Temp or the Set Point. It is
adjustable from -10 to +10 with a default value of 0.

9 Times ◆◆◆◆

LOr

With Return Water Sensor: Set to the boiler manufacturer’s specification for minimum

Low/Min Return

boiler return temperature. It is adjustable from 70° to 170°F with a default value of 70°F.

This is the highest Secondary loop water temperature the VS will maintain. Available

10 Times ◆◆◆

HI

only when Reset (r ) is selected from the Startup menu. It is adjustable from 100°F to

Hi Supply Temp

200°F with a default value of 160°F.
IMPORTANT: The VS is not a safety control. All appropriate safety controls must be installed.

11 Times

SEC

This is the temperature reading of the Secondary loop sensor. If it does not read correctly,

Default ◆◆

2nd Loop Temp ◆

check the Troubleshooting guide.

Push to

Display settings

Output Light

Indicates Status

Secondary Loop Sensor

Outdoor Sensor

Red

Push these buttons to adjust
the control settings

Digital Display defaults to read
Secondary Loop Temperature

Injection Pump

Output

Secondary Loop

Pump Output

120 VAC

Power Input

Boiler Return Sensor

Setback or remote
Enable or Disable Input

DRY CONTACT ONLY

Black

Blue

FIG. 5