beautypg.com

Design selection – Bell & Gossett P86272B VS Variable Speed Pump Control User Manual

Page 3

background image

DESIGN SELECTION

To select the correct pump, pipe size and balance valve:

1. Determine the Primary Loop Temperature. This is the

temperature the primary loop will maintain.

2. Determine the Secondary Loop Temperature. This is the

design temperature of the secondary loop. If an outdoor
reset function is being employed, this is the required
temperature of the secondary loop under maximum load.

3. Determine the design temperature drop (

᭝T or delta T) of

the secondary loop. This is the design drop in tem-
perature through the secondary loop. In most radiant
heat applications,

᭝T is 10. Other types of radiation such

as baseboard have a higher design

᭝T.

4. Determine the Maximum Injection Heat Load. This is the

maximum heat requirement of the secondary loop. The
maximum injection heat load is based on the injection
pump running at the highest speed. As the pump speed
is reduced, less heat will be delivered to the secondary
loop.

5. Use the equation below to determine the design injection

flow rate.

Design Injection Flow Rate (GPM) =

Maximum Injection Heat Load (BTU/hr)

500 (T

primary

- T

secondary

+

᭝T

secondary

) (ºF)

6. Use the table below to select the appropriate pump, pipe

size and balance valve.

Design Injection

Injection B&G Circuit

Setter

®

B&G Circuit Setter

®

B&G

Flow Rate (GPM)

Pipe Size

Balance Valve

Valve Setting

Pump

1.5

1

/

2

"

CB-

1

/

2

/ CB-

1

/

2

S

18 / 25

NRF-22

3.5

1

/

2

"

CB-

1

/

2

/ CB-

1

/

2

S

full open / 6

NRF-22

6

3

/

4

"

CB-

3

/

4

/ CB-

3

/

4

S

full open / 12

NRF-22

10

1"

CB-1 / CB-1S

full open / full open

NRF-22

15

1

1

/

4

"

CB-1

1

/

4

/ CB-1

1

/

4

S

5 / 5

NRF-22

24

1

1

/

2

"

CB-1

1

/

2

full open

NRF-33

Example:

1. Primary Loop Temp: 140ºF
2. Secondary Loop Temp: 100ºF
3. Design temperature drop: 10ºF
4. Maximum injection heat load: 150,000 BTU/hr
5. Calculate Injection flow rate

Design Injection Flow Rate (GPM) =

150,000 (BTU/hr)

=

150,000

= 6 GPM

500 (140 - 100 + 10) (ºF) 25,000

6. Injection Pipe size is

3

/

4

", full open CB-

3

/

4

balancing valve and NRF-22

Minimum of 1' of
pipe drop required
to create a thermal
trap

Rule of Thumb
3 pipe diameters
between tees

Minimum of 8 pipe diameters upstream
and 4 pipe diameter downstream of straight
pipe on either side of tees to prevent any
possibility of “jet flow” through the
common piping.

Secondary

Loop

Secondary

Loop Pump

Primary

Loop Pump

Secondary

Loop Sensor

Boiler Return

Sensor

Primary

Loop

Injection Pump

Balance

Valve

3

FIG. 2

Based on (5) feet of pipe, (4) 90° elbows, (4) tees. Correct pipe and pump size calculation for any application should be performed by a qualified engineer or contractor.