Communication protocol Serie30

Page 23/37

5.6

Function 48 : Initialise and release

Request:

DevAddr

48

CRC16_H

CRC16_L

Response:

DevAddr

48

Class

Group

Year

Week

BUF

STAT

CRC16_H

CRC16_L

Exception error:

3

If message length is incorrect

Note:

Each time the device is switched on by applying the supply voltage or after a break in the power supply, the device must be

initialised via this function. Calling a different function will lead to exception error 32.

The following information is returned:

Class

Device ID code

5:

Series 30 digital pressure transmitter (33, 35, 36, 39)

Group

Subdivision within a device class

1:

Series 30 transmitter from 1999 or later

20:

Series 30 transmitter from 2002 or later

The differences between these devices are defined in italics in the functions.

Year, Week

Firmware version

BUF

Length of the internal receive buffer

STAT

Status information

0:

Device addressed for first time after switching on.

1:

Device was already initialised