beautypg.com

Xylem Expert 7060_7070_Modbus User Manual

Page 15

background image

Communication protocol Serie30

Page 21/37

5.4

Function 32: Read configuration

Request:

DevAddr 32

Nr.

CRC16_H CRC16_L

Response:

DevAddr 32

Dates

CRC16_H CRC16_L

Exception errors:

2

If Nr. > 13

3

If message length is incorrect

32

If device has not yet been initialised

Remark:

See description function 33

5.5

Function 33: Write configuration

Request:

DevAddr 33

Nr.

Dates

CRC16_H CRC16_L

Response:

DevAddr 33

0

CRC16_H CRC16_L

Exception errors:

2

If Nr. > 13

3

If message length is incorrect

32

If device has not yet been initialised

Remark:

With those functions one can read and write some configuration of the device. This functions provide a single byte access and

replace function 100 / 101 for the devices with firmware Class.Group -Year.Week = 5.20-5.24 und earlier.