2 sensor status, Sensor status, See section 5.2 – YSI IQ S ENSOR N ET Field bus linking User Manual
Page 34: Ee section 5.2
Encoded data for field bus communication
IQ S
ENSOR
N
ET
Field bus linking
32
ba76148e01
06/2013
5.2
Sensor status
The sensor status applies to both the main and secondary measured
value of a sensor.
Code
Status
Meaning of the status
00h
UNUSED_ID
Sensor and sensor number are not available in the IQ S
ENSOR
N
ET
system.
The measured value status of the main and secondary measured
value is MISSING (4h) (see section 5.6 M
).
The UNUSED_ID status also occurs when the field bus interface of
the IQ S
ENSOR
N
ET
does not receive any data from the
IQ S
ENSOR
N
ET
controller for more than 2 minutes. Possible cause:
Communication malfunction or controller failure. The data transmitted
last remain frozen for the two minutes delay time.
01h
INACTIVE
The sensor is currently inactive. The sensor number (ID) and respec-
tive setting dataset are available in the IQ S
ENSOR
N
ET
system. The
sensor was removed from the IQ S
ENSOR
N
ET
system or the commu-
nication does not work.
The measured value status of the main and secondary measured
value is MISSING (4h) (see section 5.6 M
).
The measured value display on the terminal indicates Init or Error.