The PLC does not

contain any plausible

input data

3.6

Assigning the sensor numbers

The basis for data transmission between the superordinate control sys-
tem (PLC) and the IQ S

ENSOR

N

ET

is formed by the unique assignment

of a sensor to its sensor number (Sxx) in the IQ S

ENSOR

N

ET

system.

During the initial commissioning, the sensor numbers are assigned by
the system in the order in which the sensors are recognized by the sys-
tem.

Preparation of the IQ S

ENSOR

N

ET

for communication with a field bus

may require, e.g. the following:

Creating an IQ S

ENSOR

N

ET

system with specific assignment of sen-

sor numbers to sensors

Creating several IQ S

ENSOR

N

ET

systems with the identical assign-

ment of sensor numbers to sensors

Changing the order of the sensors in an already installed system

Creating the assignment

of sensor numbers

You want to install an IQ S

ENSOR

N

ET

system and, at the same time, to

create a specific sequence of sensor number assignments to the sen-
sors.

– Wrong setting in the

router/switch

– Correct the settings

– Blocking by firewall

– Contact your network adminis-

trator or a network specialist

Cause

Remedy

Cause

Remedy

– Input data and output data

are not consistent

– When programming the PLC,

define input data and output
data as consistent over the
entire data length

– The data interpretation of the

PLC is not correct

– Heed the data formats of the

IQ S

ENSOR

N

ET

(see also sec-

tion 4.1.3).

– Observe the data alignment of

the PLC data representation. If
necessary, exchange the
high-order and low-order bytes
word by word