Specifications, T3200 insulation monitoring relay – Littelfuse T3200 Series User Manual
Page 2
![background image](/manuals/292108/2/background.png)
Specifications
T3200 Insulation Monitoring Relay
T
32
95
-6
2E
Insulation level
0 - 5MW
Delay
1 - 10 sec.
Max. voltage
660V
Voltage range
80 - 110%
Consumption
Max. 2VA
Frequency range
45 - 65Hz
Measuring voltage
15V DC
Internal resistance
200kW
Instrument output
0 - 1mA
Instrument resistance
Max. 100W
Output relays
Normally de-energized
Contact ratings
AC: 400V, 2A, 250VA
DC: 110V, 2A, 100W
Overall accuracy
±5% of preset value
Operating temperature
-20°C to +70°C
Dielectric test
2500V, 50Hz
EMC
CE according to EN50081-1, EN50082-1, EN50081-2,
EN50082-2
Approvals
Certified by major marine classification societies
Burn-in
50 hours before final test
Enclosure material
Polycarbonate. Flame retardant
Weight
0.5kg
Dimensions
70 x 100 x 115mm (H x W x D)
Installation
35mm DIN rail or 4mm (3/16”) screws
The specifications are subject to change without notice.
Type Selection Table
Terminals
Type
1-3
2-3
Function
T3200.0010 230V
T3200.0020 450V
400V
T3200.0030 480V
415V
T3200.0040 24V DC
With 24V DC/DC converter
T3200.0050 110V
100V
T3200.0060 127V
120V
Other voltages are available on request.
Accessories
Dimensions
Weight
E2323.0010 Megaohmmeter
96x96mm
0.5kg
E2324.0010 Kiloohmmeter
96x96mm
0.5kg
E2333.0010 Megaohmmeter
144x144mm
0.8kg
Main office:
SELCO A/S
Betonvej 10
DK-4000 Roskilde
Denmark
Phone: + 45 7026 1122
Fax:
+ 45 7026 2522
e-mail: [email protected]
www.selco.com
Dimensions.
70
115
50
85
7.5
10
100
Fixing holes
2 x ø 4.5 mm
Dimensions in mm
Type Approvals and Certificates
The T3200 has been designed and tested
for use in harsh environments. The unit
is based on standard components,
providing long term durability.
The T3200 carries the CE label and has
been approved by the following marine
classification societies:
Bureau Veritas
Polish Register of Shipping
Romanian Register of Shipping
Russian Maritime Register of Shipping