Littelfuse PGR-6800 Series User Manual
Pgr-6800 series, Protection relays & controls, Motor protection–pumps (pgr 6000 family)
Protection Relays & Controls
© 2013 Littelfuse Protection Relays & Controls
Motor Protection–Pumps (PGR 6000 Family)
PGR-6800 SeRieS
Pump Protection Relay
Description
The PGR-6800 Pump Protection Relay provides protection for
pumps with three-phase motors up to 1,000 Vac. No current
transformers are required for currents up to 91 A. The protective
functions include overload, phase unbalance, phase loss, phase
sequence and undercurrent. The PGR-6800 Pump Protection
Relay is ideally suited for applications where operating without
load can induce failure. Motor current is monitored and an
undercurrent trip occurs when the current drops below a
preset level. No additional level detectors are required.
PGR-6800
SERIES
PGB-6800
(Remote Indication
and Reset Assembly)
(Pump Protection Relay)
M
L2
L1
ORdeRinG nuMbeR
COnTROL POWeR FuLL-LOad CuRRenT
PGR-6801-24
24 Vdc
7-19.6 A
PGR-6801-120
120 Vac
7-19.6 A
PGR-6801-240
240 Vac
7-19.6 A
PGR-6802-24
24 Vdc
19-44.2 A
PGR-6802-120
120 Vac
19-44.2 A
PGR-6802-240
240 Vac
19-44.2 A
PGR-6803-24
24 Vdc
40-90.4 A
PGR-6803-120
120 Vac
40-90.4 A
PGR-6803-240
240 Vac
40-90.4 A
Ordering Information
Simplified Circuit Diagram
PGB-6800 Remote Indication
and Reset Assembly
Optional remote indication of overload,
undercurrent, phase unbalance, phase loss,
and phase sequence. Remote reset included.
Accessories
A
A
aCCeSSORieS
RequiReMenT
PGB-6800
Optional
FeaTuReS
beneFiTS
No CTs required
No current transformers required for currents up
to 91 A
Adjustable trip
settings
Adjustable overload trip class setting from 5 to 15
for use with a wide variety of pumps
Output contacts
Form A and Form B ground-fault output contacts for
operation of separate annunciation and trip circuits
Remote indication
Cause-of-trip indication and reset button
Overload
Prevents insulation failures and fires; extends
motor life
Phase loss/Phase
sequence
Detects unhealthy supply conditions
Unbalance (current)
Prevents overheating due to unbalanced phases
Undercurrent
Detects low level or no-load conditions
Features & Benefits
Specifications
Protective Functions
(IEEE Device Numbers)
Input Voltage
See ordering information
Frequency
50, 60 Hz
Dimensions
H 83 mm (3.3”); W 78 mm (3.1”); D 99 mm (3.9”)
Test Button
Standard feature
Reset Button
Standard feature
Output Contacts
Isolated form A and Form B
Approvals
UL Listed (E343314)
Warranty
5 years
Mounting DIN
Overload (49, 51)
Phase sequence (46)
Undercurrent (37)
Unbalance (current) (46)
Phase loss (current) (46)