PGR-6130 SeRieS

Electronic Overload Relay

Description

The PGR-6130 Electronic Overload Relay provides protection

for small three-phase motors up to 1,000 Vac. No current

transformers are required for currents up to 91 A. The

protective functions include overload, overtemperature, phase

unbalance, phase loss, and phase sequence. The PGR-6130

Electronic Overload Relay offers dependable protection and can

be used on pumps, conveyor belts, ventilation fans and other

small-motor applications that require standard protection.

Specifications

Protective Functions

Overload (49, 51)

(IEEE Device Numbers)

Phase sequence (46)

Overcurrent (51)

PTC overtemperature (49)

Unbalance (current) (46)

Phase loss (current) (46)

Input Voltage

See ordering information

Frequency

50, 60 Hz

Dimensions

H 83 mm (3.3”); W 78 mm (3.1”); D 99 mm (3.9”)

Test Button

Standard feature

Reset Button

Standard feature

Output Contacts

Isolated Form A and Form B

Approvals

UL Listed (E343314), CE (European Union)

Warranty

5 years

Mounting DIN

ORdeRinG numbeR

COnTROL POWeR FuLL-LOad CuRRenT

PGR-6131-24

24 Vdc

4-16.7 A

PGR-6131-120

120 Vac

4-16.7 A

PGR-6131-240

240 Vac

4-16.7 A

PGR-6132-24

24 Vdc

15-40.5 A

PGR-6132-120

120 Vac

15-40.5 A

PGR-6132-240

240 Vac

15-40.5 A

PGR-6133-24

24 Vdc

40-91 A

PGR-6133-120

120 Vac

40-91 A

PGR-6133-240

240 Vac

40-91 A

motor Protection–electronic Overload (PGR 6000 Family)

Ordering Information

NOTE: External CTs can be used for full-load currents >91 A.

FeaTuReS

beneFiTS

No CTs required

No current transformers required for currents up to

91 A, simplifies installation and reduces cost

Adjustable

trip settings

Adjustable overload trip class setting from 5 to 35

to match motor characteristics

Output contacts

Form A and Form B ground-fault output contacts for

operation of separate annunciation and trip circuits

Remote indication

Allows remote cause-of-trip indication and reset

Overload

Extends motor life and prevents insulation failures

and fires

Phase loss/Phase

sequence

Detects unhealthy supply conditions

Unbalance (current)

Prevents overheating due to unbalanced phases

PTC overtemperature

Detect high ambient or blocked ventilation and

single phasing; prevents shaft/pump damage

Features & Benefits

PGB-6130 Remote Indication

and Reset Assembly

Optional remote indication of overcurrent,

phase unbalance, phase loss, phase sequence

and overtemperature. Remote reset included.

Accessories

A

aCCeSSORieS

RequiRemenT

PGB-6130

Optional

PGR-6130

SERIES

(Electronic Overload Relay)

PGB-6130

(Remote Indication

and Reset Assembly)

PTC

M

L2

L1

Simplified Circuit Diagram