Littelfuse LCP Fused Coordination PaneL User Manual
Lcp fused coordination panel, Pre-engineered solution datasheet, Selective coordination panel features/benefits
Pre-Engineered Solution Datasheet
Littelfuse.com
© 2013 Littelfuse POWR-GARD
®
Products
Rev: 011113
1 of 3
LCP Fused Coordination PaneL
Selective Coordination Panel
Features/Benefits
• Meets NEC
®
requirements
• Class CC and J fuse holders have built-in
open-circuit indication
• Fast-acting UL Listed fuses protect against short circuits
• Feed through/sub feed lugs and 84-circuit
configuration available
• Ground and neutral bars
• Copper bus standard
Advanced Design Options
• MLO, Main Circuit Breaker, or Main Fused Pullout device
• Fused Class T branch circuit pullout
• Spare fuse cabinet accessory (holds six spare fuses)
• TVSS overvoltage protection
• Any NEMA enclosure required
• High amperage sub-fed branch breakers (J60A)
• Unique Specifier Tool (see pg. 146) to easily identify panel
configurations from tens of thousands of options
Specifications
Voltage Ratings
120/208, 120/240, 277/480 VAC
Main Bus Rating
100 A - 400 A Standard
Conductor Terminals
6 AWG - 300 kcmil
UL Listed
UL 67 Panel boards and UL 50 Enclosures
Web Resources
Fuse Curves, sample requests, downloadable CAD
drawings and other technical information:
Littelfuse.com/lcp
Description
The Littelfuse
®
Coordination Panel provides a simple,
time-saving solution for circuits that require selective
coordination. This UL Listed product saves time and money,
and increases safety by minimizing system downtime.
Applications
• Elevators
• Hospitals
• Hotel and Entertainment Industry
• Amusement Parks and Stadiums
Code Requirements
Systems required by the NEC
®
to be selectively
coordinated include:
• Health Care Essential Electrical Systems (NEC 517.26)
• Elevators (NEC 620.62)
• Emergency Systems (NEC 700.27)
• Legally Required Standby Systems (NEC
701.18)
• Critical Operations Power Systems (NEC 708.54)
† Fuses quoted separately to meet panel specifications. Coordination for breakers >60 A depends on upstream and
downstream devices. More specialized configurations are also available. Contact factory for more information.
Note: The Littelfuse LPS, LPMP and LCP products are custom
designed products that fall outside standard specifications.
Custom Options (select one from each column)
number
oF
CirCuits
VoLtage
main deViCes
neutraL
rating
PaneL
mounting
PaneL
door
Fuse
HoLders
branCH CirCuit
ProteCtion deViCes
(1-3 PoLe)
†
PaneL
Feed
oPtionaL Lugs
standard
enCLosure
rating
2 - 42
120/208 V 3P, 4 W
120/240 V 1P, 3 W
277/480 V 3P, 4 W
125, 225, 400 or
600 A MLO
Up to 600 A MCB
or Main Fuse
Pullout
100%
200%
Surface
Flush
Standard
Door-in-door
30 A Class CC
60 A Class J
10 A- 60 A fused
circuit breaker
60 A-200 A
fused pullouts
Sub-fed circuit breakers
>60 A
(not fused)
Top
Bottom
None
Sub-Fed (MLO panels)
Feed-Through
NEMA 1
NEMA 3R
NEMA 4X
To quickly specify the LCP panel,
visit
Littelfuse.com/lcp
and download the Specifier Tool.