beautypg.com

Specifications, T2800 overcurrent or earth fault relay, Type selection table – Littelfuse T2800 Series User Manual

Page 2: Type approvals and certificates

background image

Specifications

T2800 Overcurrent or Earth Fault Relay

T

28

95

62

E

Dimensions.

Trip level

0.02 - 0.2 x I

N

or 0.2 - 2 x I

N

Delay

0.1 - 1.0 sec. or 1.0 - 10 sec.

Max. voltage

660V

Voltage range

60 - 110%

Consumption

Voltage 5VA at U

N

Current 0.3VA at I

N

Continuous current

2 x I

N

Frequency range

45 - 400Hz

Output relay

Normally energized, latching, resetable

Contact rating

AC: 400V, 5A, 2000VA

DC: 150V, 5A, 150W

Overall accuracy

±5%

Repeatability

±1%

Operating temperature

-20°C to +70°C

Dielectric test

2500V, 50Hz

EMC

CE according to EN50081-1, EN50082-1, EN50081-2,

EN50082-2

Burn-in

50 hours before final test

Enclosure material

Polycarbonate. Flame retardant

Weight

0.5kg

Dimensions

70 x 100 x 115mm (H x W x D)

Installation

35mm DIN rail or 4mm (3/16”) screws

The specifications are subject to change without notice.

Type Selection Table

Standard types: I

N

= 5A

Terminals

Type

1-3

2-3

I

N

T2800-00

230V

5A

T2800-01

450V

400V

5A

T2800-02

127V

120V

5A

T2800-04

24V DC+AC

5A

T2800-05

480V

415V

5A

T2800-08

230V

1A

Other combinations and voltages are available on request.

9

5

10

6

18
19

8

7

I x 10

N

12

1

15
16

13

LATCHING

OFF

SEC x 10

3

2

Fig. 2. Relay shown deenergized

Main office:

SELCO A/S

Betonvej 10

DK-4000 Roskilde

Denmark

Phone: + 45 7026 1122

Fax:

+ 45 7026 2522

e-mail: [email protected]

www.selco.com

70

115

50

85

7.5

10

100

Fixing holes

2 x ø 4.5 mm

Dimensions in mm

Type Approvals and Certificates

The T2800 has been designed and tested

for use in harsh environments. The

unit is based on standard components,

providing long term durability.

The T2800 carries the CE label and has

been approved by the following marine

classification societies:

Bureau Veritas

Russian Maritime Register of Shipping