Specifications, T2800 overcurrent or earth fault relay, Type selection table – Littelfuse T2800 Series User Manual
Page 2: Type approvals and certificates
![background image](/manuals/292012/2/background.png)
Specifications
T2800 Overcurrent or Earth Fault Relay
T
28
95
62
E
Dimensions.
Trip level
0.02 - 0.2 x I
N
or 0.2 - 2 x I
N
Delay
0.1 - 1.0 sec. or 1.0 - 10 sec.
Max. voltage
660V
Voltage range
60 - 110%
Consumption
Voltage 5VA at U
N
Current 0.3VA at I
N
Continuous current
2 x I
N
Frequency range
45 - 400Hz
Output relay
Normally energized, latching, resetable
Contact rating
AC: 400V, 5A, 2000VA
DC: 150V, 5A, 150W
Overall accuracy
±5%
Repeatability
±1%
Operating temperature
-20°C to +70°C
Dielectric test
2500V, 50Hz
EMC
CE according to EN50081-1, EN50082-1, EN50081-2,
EN50082-2
Burn-in
50 hours before final test
Enclosure material
Polycarbonate. Flame retardant
Weight
0.5kg
Dimensions
70 x 100 x 115mm (H x W x D)
Installation
35mm DIN rail or 4mm (3/16”) screws
The specifications are subject to change without notice.
Type Selection Table
Standard types: I
N
= 5A
Terminals
Type
1-3
2-3
I
N
T2800-00
230V
5A
T2800-01
450V
400V
5A
T2800-02
127V
120V
5A
T2800-04
24V DC+AC
5A
T2800-05
480V
415V
5A
T2800-08
230V
1A
Other combinations and voltages are available on request.
9
5
10
6
18
19
8
7
I x 10
N
12
1
15
16
13
LATCHING
OFF
SEC x 10
3
2
Fig. 2. Relay shown deenergized
Main office:
SELCO A/S
Betonvej 10
DK-4000 Roskilde
Denmark
Phone: + 45 7026 1122
Fax:
+ 45 7026 2522
e-mail: [email protected]
www.selco.com
70
115
50
85
7.5
10
100
Fixing holes
2 x ø 4.5 mm
Dimensions in mm
Type Approvals and Certificates
The T2800 has been designed and tested
for use in harsh environments. The
unit is based on standard components,
providing long term durability.
The T2800 carries the CE label and has
been approved by the following marine
classification societies:
Bureau Veritas
Russian Maritime Register of Shipping