Description
The PGR-6150 Motor Protection System provides 13 protective
functions by utilizing both current and temperature inputs. It is
a modular system consisting of the control unit and an operator
interface (PGR-6150-OPI). The OPI allows programming and
displays metered values. The PGR-6150 is used to provide
current- and temperature-based protection, metering and data
logging for three-phase motors used in industrial environments.
Current transformers are not required for currents up to 25 A.
Control Unit
g
Integrated phase CTs (external for applications > 25 A)
g
Ground-fault CT input
g
One PTC input and one programmable input
g
Two programmable output contacts
g
Eight status LEDs
g
RS-485 Communications
g
DIN-rail mountable
g
PC interface software
Operator Interface (optional)
g
Large, bright, LCD display
(2 x 20 alphanumeric characters)
g
Keypad for menu selection (system parameters,
measurements, and fault reports)
g
Displays metered values
g
Six user-programmable LEDs
g
Powered by Control Unit
g
1 meter (39-inch) connection cable included
ORdeRinG nuMbeR
COnTROL POWeR
PGR-6150-24 (Control Unit)
24/48 Vdc
PGR-6150-120 (Control Unit)
120/240 Vac/dc
PGR-6150-OPI (Operator Interface)
Powered by Control Unit
Ordering Information
NOTE: External CTs can be used for full-load currents >25 A.
PGR-6150-OPI Operator Interface
Optional Operator Interface for displaying
metered values and programming
PGC-6000 Series Ground-Fault Transformer
Optional zero-sequence current transformer,
used to measure ground-fault current.
Required for applications >25 A.
Accessories
A
B
aCCeSSORieS
RequiReMenT
PGC-6000 Series
Optional
1
1
A
A
Simplified Circuit Diagram
M
PGR-6150
PTC
(Operator Interface)
(Motor Protection System)
PGR-6150-OPI
L2
L1
GF CT
B
A
1
Littelfuse.com/pgr-6150
Rev: 4-A-050213
Based on Manual Rev 1