beautypg.com

Littelfuse FPS Series User Manual

Fps series, Protection relays & controls, Feeder protection–advanced

background image

Protection Relays & Controls

© 2013 Littelfuse Protection Relays & Controls

Littelfuse.com/fps

PHASE CT

PHASE CT

GF CT

PHASE CT

L2

FPS-CTU

L1

FPS-OPI

(Control Unit)

(Operator Interface)

Feeder Protection–Advanced

FPS SERIES

Feeder Protection System

1

2

Description

The FPS Feeder Protection System monitors voltage
and current to provide a comprehensive package of
17 protective functions. The FPS is a modular system
with integrated protection, breaker control, metering,
and data-logging functions.

Operator Interface (FPS-OPI)

g

Large, bright, 4 x 20 vacuum-fluorescent display

g

Display metered values

g

Access set points

g

Powered by Control Unit

g

Panel mount or attach directly to Control Unit

g

Remote mounting (1.2 km or 4000 ft maximum loop length)

g

1/2 DIN size

g

Hazardous-location certified

Control Unit (FPS-CTU)

g

Current inputs—5-A or 1-A secondary phase

current transformers

g

Voltage inputs—up to 600 V without PTs

g

Earth-leakage input—5-A or 1-A secondary or

sensitive transformer

g

8 digital inputs, 5 relay outputs, 1 analog input and output

g

24-Vdc supply for OPI and RTD modules, and for digital inputs

g

IRIG-B time-code input

g

1/2 DIN size, surface mount

g

RS-485 network communications (Standard)

g

DeviceNet

, Profibus

®

, or Ethernet communications available

1

2

Phase Current Transformers

Phase CTs are required to detect phase

currents.

Ground-Fault Current Transformer

Zero-sequence current transformer detects

ground-fault current. Available with 5-A

and 30-A primary ratings for low-level pickup.

MPS-RTD Temperature Input Module

Optional module provides 8 inputs to connect

Pt100, Ni100, Ni120, and Cu10 RTDs.

SE-IP65CVR-M Cover

Optional gasketed, transparent cover for

limited access and IP65 protection for an

Operator Interface Module.

B

C

D

Accessories

A

AccESSoRIES

REquIREmEnt

FPS-OPI-01-00

Recommended

SE-IP65CVR-M

Optional

Phase CTs

Required

Ground-Fault CT

Recommended

MPS-RTD

-01-00

Optional

1

2

oRdERIng numbER

communIcAtIonS

FPS-CTU-01-00

RS-485

FPS-CTU-02-00

RS-485 & DeviceNet

FPS-CTU-03-00

RS-485 & Profibus

®

FPS-CTU-04-00

RS-485 & Ethernet

Ordering Information

Simplified Circuit Diagram

B

A

Rev: 4-A-050213

Based on Manual Rev 0