Littelfuse LD Series User Manual
Powr-bloks, Powr-gard, Blocks and holders datasheet
Littelfuse.com
© 2013 Littelfuse POWR-GARD
®
Products
POWR-GARD
®
Blocks and Holders Datasheet
Rev: 062613
1 of 6
Specifications
Voltage Rating
600 V
Current Rating
Based on NEC Table 310.16, using 75°C copper wire
Material
Phenolic rated at 150°C and Thermoplastic
rated at 125°C (LD1400 and LS1300 series only)
Connector
Standard: Highly con duc tive aluminum, tin plated
Copper: Highly conductive copper, tin plated
Flammability Rating UL94 V-0
Approvals
UL Recognized - LD/LS Series (File: E171395)
LFD/LFS Series (File: E309688)
CSA Certified - LD/LS Series (File: LR700111)
LFD/LFS Series (File: 007316_0_000)
Environmental
RoHS compliant, Lead (Pb) free
Ordering Information
See Selection Guide on next page
Web Resources
For dimension, CAD and 3-D drawings, visit:
Littelfuse.com/powrbloks
powr-bloks
™
Distribution Blocks • Splicer Blocks • Covers
Description
POWR-BLOKS
TM
power distribution blocks offer a safe,
convenient way of splicing cables, providing a fixed junction
tap-off point or splitting primary power into secondary
circuits. Lx2xxx-DIN series offers integral DIN-Rail mount
and an optional hinged safety cover.
Optional power distribution block covers provide protection
against accidental shorting between poles caused by
loose wires, tools, or other conductive material. They also
protect personnel from accidentally contacting energized
connectors. To order protective covers, match the number
of poles for the block to the cover.
Applications
Typical applications include heating, air conditioning and
refrigeration systems, el e va tor systems, material handling
equipment, control panels, motor controls, switchgear,
and anywhere power needs to be distributed to more
than one load.
Connectors
Box lug connectors are designed for use with a single, solid
or class B or C stranded conductor. Use of more than one
con ductor per connector opening or use of extra-flexible,
fine-stranded conductors, such as welding cable, voids the
UL Listing and may cause overheating. Manufacturers of
cable ter minations can furnish crimp-on sleeves for fine
stranded conductors which permit these conductors to be
used with box lugs.
Ampere Ratings
The ampere rating per pole for power distribution blocks is
based on the line ampacity of 75°C insulated conductors per
NEC
®
Table 310.16. If 60°C insulated conductors are used,
load must not exceed the ampacity of 60°C conductors.
Use of conductors rated in excess of 75°C is permitted (for
example 90°C), however, load must not exceed the ampacity
of 75°C conductors.
Hinged Plastic Covers
Catalog/
ordering
number
For use with
distribution/spliCer bloCk no.
poles
0LCH1321Z
LD2xxx-1DIN / LS2xxx-1DIN
1
0LCH1322Z
LD2xxx-2DIN / LS2xxx-2DIN
2
0LCH1323Z
LD2xxx-3DIN / LS2xxx-3DIN
3
Note: Optional hinged covers snap on to blocks.
Clear Plastic Covers
Catalog/
ordering
number
For use with
distribution/spliCer bloCk no.
poles
LPBC02
LD0xxx-2 / LS0xxx-2
2
LPBC03
LD0xxx-3 / LS0xxx-3
3
LPBC21
LD2xxx-1 / LS2xxx-1
1
LPBC22
LD2xxx-2 / LS2xxx-2
2
LPBC23
LD2xxx-3 / LS2xxx-3
3
LPBC31
LD3xxx-1 / LS3xxx-1
1
LPBC32
LD3xxx-2 / LS3xxx-2
2
LPBC33
LD3xxx-3 / LS3xxx-3
3
LPBC41
LD4xxx-1 / LS4xxx-1
1
LPBC42
LD4xxx-2 / LS4xxx-2
2
LPBC43
LD4xxx-3 / LS4xxx-3
3
LPBC51
LD5xxx-1 / LS5xxx-1
1
LPBC52
LD5xxx-2 / LS5xxx-2
2
LPBC53
LD5xxx-3 / LS5xxx-3
3
Note: For installation of optional clear plastic covers, use the screws provided with each
cover.