beautypg.com

Littelfuse T4400 Series User Manual

Page 2

background image

Supply voltage / current
The supply voltage from L1 and L2 is

connected to terminals 1 and 3 or 2 and

3, depending on the system voltage.

The measuring current from L3 is

connected to terminals 5 and 6 with 5

referring to the generator (see the

application diagram on page 3). The

current measurement must be taken

from the same phase on all generators.

The current is measured in the phase

that is not supplying the unit. It is

important to ensure that the phase

sequence is correct.

This relation between the connections of

voltage and current must be correct in

order to achieve a correct load measure-

ment. It can be checked on terminal 11

(TEST OUT), where an input of nominal

current (1A or 5A) and power factor 1.0

gives +6V for correct connection.

Ramp function
The T4400 includes a ramp function.

With this function activated, the unit

will smoothly take over the load up to

load balance.

In order to activate this function,

terminals 7 (UNLOAD) and 32 should

initially be bridged and so should

terminals 31 (C/B) and 32 (for example

with an aux. contact of the circuit

breaker). Now the ramp function can be

activated by opening the connection

between terminals 7 (UNLOAD) and 32.

Common reference
Terminal 12 (COM.) is the common

reference for terminals 8 to 13.

Unload facility
The unload facility will smoothly

unload the generator. This facility

works like an inverted ramp function. If

activated, the load on the generator will

be reduced and maintained at a low

level.

In order to activate, terminals 31 (C/B)

and 32 should initially be bridged. The

unload function is then activated by

connecting terminal 7 (UNLOAD) to 32.

Unload trip
When the load passes below 5% load, a

trip signal is provided as a normally

open (NO) contact on terminal 20-21

and a normally closed (NC) contact on

21-22. This trip signal can be used to

trip the circuit breaker.

Reverse power trip
The reverse power trip operates at 10%

with a delay of 10 sec., but it can be

reduced to 5% by bridging terminals 17

and 18 and to 5 sec. delay by bridging

18 and 19. A resistor of 510kW between

17 and 18 gives 7.5%, a resistor of 2.7MW

between 18 and 19 gives 7.5 sec. delay.

The trip signal is provided as a normally

open (NO) contact on term. 23-24 and a

normally closed (NC) contact on 24-25.

Frequency control
The electronic speed controller will

control the frequency of the generator.

However, the frequency control of some

speed controllers will drift with time. In

order to compensate for this, the T4400

includes frequency control.

The system frequency can be set to

60Hz with terminals 29 and 30 bridged

or 50Hz with these terminals open.

Further adjustment of the frequency is

possible using the potentiometer DIFF.

FREQ. on the front panel.

Connecting terminal 8 (FREQ. OUT) to

12 will disable the frequency control.

This is used when running parallel with

the grid, where the frequency is fixed by

the grid.

Input from synchronizer
Between terminals 9 (FREQ. IN) and 12

the SELCO T4000 Auto Synchronizer or

most other synchronizer makes can be

connected. The synchronizer will then

give the synchronizing output through

the T4400. This signal is not affected by

the output adjustments on the T4400.

External power measurement
Between terminals 10 (WATT IN) and 12

a negative voltage (0 to -1V DC from a

watt converter) can be connected to

substitute the internal load measuring

circuit. In this case no input on terminals

5 and 6 is needed. Most standard measu-

ring signals can be adapted with external

resistors.

0-10V : series resistor 510kW

0-5mA : parallel resistor 200W

Communication between load sharers
For communication between the load

sharers all terminals 12 (COM.) are

interconnected, as well as all terminals

13 (+).

Output to the speed controller
Output to the electronic speed controller

is taken from terminals 15 (REF.) and 16

(+) with terminal 15 as reference. If an

inverse signal is needed, use terminals

15 (REF.) and 14 (-) rather than changing

wires to 15 and 16. The output signal is

an integrated signal. This means, the

output signal will change as long as

there is a load deviation. When load

balance is obtained the output signal will

stay at its current level.

Adjustments

LOAD DEV.

can be used for fine adjust-

ments of the load balance. LOAD DEV.

should also be used to obtain balance

with generators of different size and with

different types of current transducers

(CTs). For generators of same size and

with same type of CT, the setting 0

should be used on all load sharers.

DIFF. FREQ.

is used for adjustment of

system frequency as described on page

2 in the section about frequency control.

If the system frequency should be

exactly 50 Hz or 60 Hz, the setting 0

should be used.

STABILITY

is used for adjusting the

regulation time. A high setting of

STABILITY will give a slow but

accurate regulation. A low setting will

give a fast regulation. However, a too

low setting may cause instability.

VARIABLE OUT

is intended for

adjusting the size of the output signal to

the speed controller. The output

increases with higher setting on the

potentiometer. Too much output can

result in instability. If this is the case,

turn the potentiometer anti clockwise

until stability is restored.

Interfacing

A detailed note on interfacing the T4000

and the T4400 to a wide number of

different electronic speed controllers is

available from SELCO. This note can

also be downloaded from our web-site

www.selco.com.

Trouble Shooting

If load balance is not obtainable
If load balance is not obtainable and the

power goes to maximum or reverse

power, one of the signals is inverted

due to wrong polarity or interchanged

wires. If this is the case, the following

should be checked:

1. The polarity of the power measuring

signals on terminal 11 (TEST OUT)

must be positive with the generator

on load. If the polarity is negative,

change the voltage connections 1 and

3 or 2 and 3 or the current connections

5 and 6.