1.10 EMC

The shortening "EMC" stands for the Electro Magnetic Compatibility. According to the EMC
directive "the apparatus shall be so constructed that:
a) The electromagnetic disturbance it generates does not exceed a level allowing other apparatus

to operate as intended

b) The apparatus has an adequate level of intrinsic immunity of electromagnetic disturbance to

enable it to operate as intended."

Technical
construction file

The technical construction file describes how the frequency converters
have been constructed to comply with the directive and standard
requirements.

Declaration of
conformity

With the declaration of conformity the manufacturer informs that device
is manufactured to fulfill required EMC standards.

CE-mark

The CE marking is a declaration by a manufacturer or importer located
in the European Economic Area that a product complies with the safety
and health requirements of the directive in question. The manufacturer
demonstrates for the authorities that the product complies with the safety
requirements within the EU.

Environments

Immunity and emission requirements are divided in two levels in the
product standard according to the environments.

First environment means environment that
includes domestic premises an also
establishments directly connected to a
low-voltage power supply network.

PDS

Second environment means environment
that includes all establishments other than
those directly connected a low-voltage
power supply network.

PDS

1.10.1 Fulfilled EMC-standards

Immunity

D2H/D2C fulfill the immunity requirements defined in the EN 61800-3
Amendment 11 (2000) for the second environment.

Emissions

D2H/D2C fulfill the emission requirements of the EN 61800-3 A11 2000
for the second environment.

Immunity level of
second environment

Emission limit of
second environment

Emission limit of
first environment

Typical emission
of D2H/D2C

Safety margin

Interference
level

Frequency