6

Input signals (Segment 6): User can choose one function for a Segment from below table.

*Input signal (Segment 6):

Description

Meaning “1”

“0”

Battery mode shutdown

Only Battery mode

shutdown

Normal

Any mode shutdown

Shutdown

Normal

Emergency power off

OFF

Normal

Remote On/Off

OFF

ON

Input signals (Segment 7): Segment 7 is fixed to UPS On function.

*Input signal (Segment 7):

Description

Meaning “1”

“0”

UPS On

ON

Normal

Input signals (Segment 8): Segment 8 is fixed to UPS Off function.

*Input signal (Segment 8):

Description

Meaning “1”

“0”

UPS Off

OFF

Normal

Configuring the Card Introduction

1. General

This document specifies the Serial communication protocol of the Dry contact Management Card. The

card provided the following features.

(1) Get UPS internal information by SCI protocol

(2) Bridge communication data between PC and ups

(3) Configure five output relay signal

(4) Configure one input signal for shutdown ups or remote on/off

(5) Configure Dry contact normal open and normal close status

(6) Configure Dry contact function definition

(7) Configure Dry contact active delay time