PowerWalker AS_400 Card 3 User Manual
Page 16
16
-----------------------------------------------------------------------------
Segment 6 Function
-----------------------------------------------------------------------------
1. Battery Mode Shutdown
2. Any Mode Shutdown
3. Emergency Power Off
4. Remote On/Off
0. Exit
-----------------------------------------------------------------------------
Please Enter Number:
Figure19. Input function select menu
Function description:
1. Battery Mode Shutdown: If Signal is active and UPS is under bat mode, UPS will cutoff output
2. Any Mode Shutdown: If Signal is active and UPS is under any mode, UPS will cutoff output
3. Emergency Power Off: If Signal is active and UPS is under any mode, UPS will cutoff output,
give out EPO warning, and pressing any button on UPS LCD panel
can not turn on UPS.
4. Remote On/Off: If Signal is active (close Pin 8 & Pin1 when Segment 6 is configured to Normal
Open; or open Pin 8 & Pin1 when Segment 6 is configured to Normal Close )
and UPS is under any mode, UPS will cutoff output.
If Signal is not active (open Pin 8 & Pin1 when Segment 6 is configured to
Normal Open; or close Pin 8 & Pin1 when Segment 6 is configured to Normal
Close ) and UPS is under any mode, UPS will turn on.
When Figure18. Input Segment select menu Type 2 or 3 and press Enter, it will reject the number
because Segment 7 or 8 function is fixed. User only can type 1 to set Segment 6 function. If user
type 0, the menu will return to Figure12. Main menu
This Segment Function can not be set.
Please Enter a Number again:
Figure20. Segment function can not be set
4.6. Function Segment Active Delay Time menu
When main menu Type 4 and press Enter. The menu displays the Function Segment Active Delay
Time and current setting value as below, in this menu type 0, the menu will return to Figure12.
Main menu