Velleman CU2200 User Manual

Page 9

background image

CU2200

v

3-02

26.10.2012

©

Velleman nv

9

SMS Message Contents

Command 8 is used to program the alarm message contents. The CU2200 will reply to the mobile

phone with the programmed message for that alarm channel.
Command: PWD:XXXX,READYTEXT%

XXXX Password
Y

Alarm channel number (1 ~ 8)

Commanding the CU2200 to Send SMS Message

This command is used to make the CU2200 to send the SMS message for testing purposes.
Command: PWD:XXXX,SENDMSA:XB%

XXXX Password
A

Phone number (1 ~ 8)

XB

SMS message selection

00: schedule health check status

01:closed triggered alarm channel 1, SMS message

02: closed triggered alarm channel 2, SMS message
03: closed triggered alarm channel 3, SMS message

04: closed triggered alarm channel 4, SMS message

05: closed triggered alarm channel 5, SMS message
06: closed triggered alarm channel 6, SMS message

07: closed triggered alarm channel 7, SMS message

08: closed triggered alarm channel 8, SMS message
09:manual input message

10:Low voltage alarm message

11:AD channel 1, SMS message

12:AD channel 2, SMS message
13:Open triggered alarm channel 1, SMS message

14: Open triggered alarm channel 2, SMS message

15: Open triggered alarm channel 3, SMS message
16: Open triggered alarm channel 4, SMS message

17: Open triggered alarm channel 5, SMS message

18: Open triggered alarm channel 6, SMS message
19: Open triggered alarm channel 7, SMS message

20: Open triggered alarm channel 8, SMS message

Example:

PWD:1234,SENDMS4:09,Good Morning%

Password 1234
SMS message “Good Morning” will be sent to phone number 4.

Error message about setting A:

Number Choice Miss

A is not within 1 ~ 8

Number Non Exist No phone number is preset in that location

Error message about setting XB

Did not specify SMS contents

XB is not within 00 ~20

Reply confirmation message:

Success!:

CU2200 succeeds in sending message.

Failed!:

Operation failed but phone number exists.

Relay Output Control

Command: PWD:XXXX,COUTN:Y%

Password 1234
N

Relay output channel (1 ~ 3) (outputs 2 and 3 not available)

Y 1

0

Turn on (close) the output
Turn off (open) the output

The relay output is N.O. by default.

Command COUTN:1 is not valid when the relay output is triggered by alarm. Reply message will be
ST:XXX in this case.

In the above case, command COUTN:0 is used to reset the relay output after the alarm is triggered.

Relay Output Delay Time

Command: PWD:XXXX,OUTNDLAY:YYYY%

XXXX Password
N

Relay output channel (1 ~ 3) (outputs 2 and 3 not available)

YYYY

0000 – 9999 seconds

0000 Turn the output on or off (default)

0005 Turn on the output for 5 seconds and off again

Turn off the output for 5 seconds and on again

The relay output delay time is good for controlling e.g. an electric door lock.