• Operating Voltage Low Level Alarm Message
When the power supply voltage level is below the minimum level at 5.34VDC, the CU2200 will send
an alarm SMS message.
Date 2007-06-15
Time 13:25
ST:001;TM200706121325;V:5.34#
• Operating Voltage Low Level Alarm
This command is used to set the action to be taken once the operating voltage drops below 7.0VDC.
Value of the current operating voltage can be retrieved by command 2.
Command: PWD:XXXX,ADCOUT0:YY,ZZZZBBBB,NNN%
XXXX Password
YY
00 means alarm not reported to control centre
10 means alarm reported to control centre 1
01 means alarm reported to control centre 2
11 means alarm reported to control centre 1 and 2
ZZZZBBBB
Selection of the alarm phone dial and alarm SMS
0 means no alarm report
1 means SMS only
2 means phone dial only => (Phone dial not available)
3 means SMS first, then phone dial =>(Phone dial not available)
Z Z Z Z
1
st
2
nd
3
rd
4
th
phone number
B B B B
5
th
6
th
7
th
8
th
phone number
NNN
Relay output control
0 means no relay output control
1 means relay output triggered by alarm
N N N
1
st
2
nd
3
rd
relay output
(2
nd
and 3
rd
relay output not available)
• Arm/Disarm Setup
Command: PWD:XXXX,ARM%
XXXX Password
Example:
PWD:1234,ARM%
Password 1234
Unit is armed and in alert status
Command: PWD:XXXX,DISARM%
XXXX Password
Example:
PWD:1234,DISARM%
Password 1234
Unit is disarmed and no alarm is reported
c.
System Information Report
• Default Setting
Command: PWD:1234,PARAMETER1%
ST:000;T:2006/10/01/01:01;H:1;F1:,00;F2;,00;XH:31#
Command: PWD:1234,PARAMETER2%
ST:000;VL:7.00,O:00,0000,000;A1M:5.000,0.000,1.000,0,5.000,0.500,O:00,00000000,000;A2M:
5.000,0.000,1.000,0,5.000,0.000,O:00,00000000,000#
Command: PWD:1234,PARAMETER3%
ST:000;K1:1,O:00,00000000,000;K2:1,O:00,00000000,000;K3:1,O:00,00000000,000;K4:1,O:00,
00000000,000;K5:1,O:00,00000000,000;K6:1,O:00,00000000,000;K7:1,O:00,00000000,000;K8:
1,O:00,00000000,000#
Command: PWD:1234,PARAMETER4%
ST:000;C1:,1;C2:,1;C3:,1;C4:,1;C5:,1;C6:,1;C7:,1;C8:,1;#
• System Parameters RESET
Command: PWD:XXXX,PARAMETER&%
[SMS message received]
Parameter initialize success!