EMCP 4.2 GENERATOR SET CONTROLLER
0
OPTIONAL MODULES
RTD MODULE
The RTD module serves to provide expandable
generator temperature monitoring capability of the
EMCP 4 and is capable of reading up to eight type
2-wire, 3-wire and 4-wire RTD inputs. The RTD
Module has been designed for use on the
Accessory Communication Network and may be
used in either local (package mounted) or remote
(up to 800 feet) application. A maximum of one RTD
Module may be used with a single EMCP 4.2.
THERMOCOUPLE MODULE
The thermocouple module serves to provide
expandable engine and generator temperature
DIGITAL INPUT/OUTPUT MODULE
monitoring capability of the EMCP 4 and is
The Digital Input/Output (DI/O) module serves to
capable of reading up to twenty Type J or K
thermocouple inputs. The thermocouple
provide expandable Input and Output capability
of the EMCP 4 and is capable of reading 12 digital
module has been designed for use on the
accessory communication Network and may be
used in either local (package mounted) or remote
(up to 800 feet) application. A maximum of one
thermocouple modules may be used with a single
EMCP 4.2 on each datalink.
inputs and setting 8 relay outputs. The DI/O
module has been designed for use on the accessory
Communication Network and may be used in
either local (package mounted) or remote
(up to 800 feet) application. A maximum of four DI/O
modules may be used with a single EMCP 4.2.
LEHE0138-0
4
Information contained in this publication may be considered confidential. Discretion is recommended when distributing.
Materials and specifications are subject to change without notice.
CAT, CATERPILLAR, their respective logos, “Caterpillar Yellow,” the “Power Edge” trade dress as well as corporate
and product identity used herein, are trademarks of Caterpillar and may not be used without permission.
©2010 Caterpillar
All Rights Reserved.
LEHE0138-00 (03-10)
Printed in U.S.A