Communication, Environmental specifications, Standards – Milton CAT D175-2 175 kW Controller Specifications User Manual
Page 2: Features/benefits (cont’d) standard features
E M C P 3 . 2
G E N E R A T O R S E T C O N T R O L L E R
LEHE4942-02
2
●
Set points & software are stored in nonvolatile
memory, preventing loss during a power outage.
●
Compatibility with both mechanical and
electronic engines makes it versatile.
●
True RMS sensing ensures AC metering accuracy
to within ± 1% of rated AC voltage (L-L and L-N)
and current.
●
kW and kVA metering to within ± 5% of rating.
●
Three levels of security allow for configurable
operator privileges.
●
Single, standard 70-pin connector
COMMUNICATION
●
J1939 (Primary Data Link)
●
J1939 #2 (Accessory Data Link)
●
MODBUS RTU (1/2 duplex); RS-485
(Customer Communication)
ENVIRONMENTAL SPECIFICATIONS
●
Environmentally sealed front face rated for
IP56. Resistant to chemical splash, including:
diesel fuel, engine oil and machine oil.
●
Protection level IP22 for rear of controller
●
Resistant to salt spray
●
Vibration: withstands 4.3G @ 24-1000 Hz
●
Shock: withstands 15G
●
Monitoring Functionality & Controls
Operational from –40° C to 70° C
(–40° F to 158° F)
●
Display Operational from –20° C to 70° C
(–4° F to 158° F)
●
Storable from –40° C to 85° C (–40° F to 185° F)
●
0 to 95% Humidity, non-condensing from 30° C
to 60° C (86° F to 140° F)
STANDARDS
●
UL Recognized
●
CSA C22.2 No.100,14, 94
●
Complies with all necessary standards for
CE Certification
98/37/EC Machinery Directive
– BS EN 60204-1 Safety of Machinery
89/336/EEC EMC Directive
– BS EN 50081-1 Emissions Standard
– BS EN 50082-2 Immunity Standard
73/23/EEC Low Voltage Directive
– EN 50178 LVD Standard
●
ISO3046, ISO8528
●
IEC529, IEC60034-5, IEC61131-3
●
MIL STND 461
CONTROLS
●
Auto/Start/Stop
●
Engine Cool-Down timer
●
Emergency Stop
●
Engine Cycle Cranking
●
Lamp Test
●
Generator Voltage
●
Engine Speed/Generator Frequency
DIGITAL (LCD) INDICATION
●
Generator AC Voltage – 3 phase (L-L & L-N)
●
Generator AC Current (per phase & average)
●
Generator Power kW (total & per phase)
●
Generator kVAR (total & per phase)
●
Generator kVAR-hr (total)
●
Generator % of rated power (total)
(kW, kVA, kVAR)
●
Generator kVA (total & per phase)
●
Generator kW-hr (total)
●
Generator Power Factor (PF)
(average & per phase)
●
Generator Frequency
●
Engine RPM
●
Battery Voltage
●
Engine Hours
●
Engine Successful Start Counter
●
Engine Oil Pressure
●
Engine Coolant Temperature
●
Engine Crank Attempt Counter
●
Service Maintenance Interval
(Engine Operating Hours or Calendar Days)
●
Real Time Clock
●
Twenty (20) Event Fault Log
Notes:
1. Temperature indications are viewable in either
°C or °F (operator selectable)
2. Pressure indications are viewable in psi, kPa,
or bar
3. Fuel Consumption viewable in US/Imperial
gal/hr or Liters/hr
FEATURES/BENEFITS (CONT’D)
STANDARD FEATURES