Addressable control module trigger output, Green lead, Hookup diagram – Altronix AL642ULADA Installation Instructions User Manual

Page 7: Fig. 2b fig. 2a, Wire smoke detector, Magnetic door holder

background image

AL642ULADA

- 7 -

Fig. 2

* Indicates existing trouble condition. When a trouble condition (open, short or ground) occurs on a specific output, the
corresponding red output LED, [OUT1-OUT4] will blink. The corresponding green input LED will blink as well.

** Indicates trouble condition memory. When a trouble condition restores, the units red output LEDs, [OUT1-OUT4]
will blink with a shorter and distinctly different duration. The green input LEDs will be off (normal condition).
To reset the memory depress the reset button located on the AL842LGK logic board (Fig. 2c, pg. 7).
The LED(s) will extinguish.

Note: When indicating circuits have restored, trouble memory reset is not required for normal operation.

Hookup Diagram:

Fig. 2b

Fig. 2a

OUT1 OUT2 OUT3 OUT4

INP2 INP1

FAULT

RESET

OUT1

OUT3

OUT2

OUT4

IN>OUT SYNC
STROBE SYNC

TEMPORAL

INPUT SELECT

IN>OUT SYNC
STROBE SYNC

TEMPORAL

INPUT SELECT

NC C NO C "F

AUL

T" NC

+ DC ---

-- AUX2 +

-- LOOP4 +

-- OUT4 +

-- OUT3 +

-- LOOP3 +

-- LOOP1 +

-- OUT1 +

-- OUT2 +

-- LOOP2 +

-- IN1 +

-- RET1 +

-- IN2 +

-- RET2 +

NC "DRY1" C

NC "DRY2" C

-- AUX1 +

Green Lead

AC Local

Supervised

Non-power limited

Addressable

control module

trigger output

(See Typical Application Diagram for device hookup)

Regulated Power-Limited Outputs 2.5 amp max.

per output max.

(total = 6.5 amp)

(Supervised)

Non-Supervised

+ --

4-wire Smoke

Detector

+ --

4-wire Smoke

Detector

Fire

Alarm

Control

Panel

(FACP)

EOL Power

Supervision Relay

(Not Supplied)

EOL Resistor

from FACP

Common

Trouble output to Digital

Communicator or Local

Annunciator Dr

y

output Contact

(Form "C" contacts)

(non-super

vised)

This connection is used to monitor
AC and Bat Fail and will cause a
simultaneous trouble condition
to the FACP's IN1 and IN2
(Non-Supervised)

Factory Installed

Board Interface

Cable

Divider

AC

Non-power limited

unswitched 120VAC

60Hz, 5 amp
power mains

(non power-limited)

Line

Ground

Neutral

Magnetic

Door Holder

Non-Super

vised

Supervised

Non-Supervised

Power Limited Inputs

5A

250V

AC TROUBL

E

DELA

Y

OPTION

AC
FA
IL

NC C NO

BA
T

FA
IL

NC C NO

NC

C

NO

C "F

AUL

T" NC

Fig. 2c

Trouble Memory

Reset Button

+ DC

---

BA
T

FA
IL

NO C NC NO C NC

+ BA

T
---

L

G

N

DC

AC
FA
IL

AC

15A

32V

10A

250V

OUT1 OUT2 OUT3 OUT4

INP2 INP1

FAULT

RESET

OUT1

OUT3

OUT2

OUT4

IN>OUT SYNC

STROBE SYNC

TEMPORAL

INPUT SELECT

IN>OUT SYNC

STROBE SYNC

TEMPORAL

INPUT SELECT

NC C NO C "F

AUL

T" NC

+ DC ---

-- AUX2 +

-- LOOP4 +

-- OUT4 +

-- OUT3 +

-- LOOP3 +

-- LOOP1 +

-- OUT1 +

-- OUT2 +

-- LOOP2 +

-- IN1 +

-- RET1 +

-- IN2 +

-- RET2 +

NC "DRY1" C

NC "DRY2" C

-- AUX1 +

Green Lead

Addressable

control module

trigger output

(See Typical Application Diagram for device hookup)

Power-Limited Outputs 2.5 amp per output max.

(total = 10 amp)

+ --

4-wire Smoke

Detector

+ --

4-wire Smoke

Detector

Fire

Alarm

Control

Panel

(FACP)

EOL Power

Supervision Relay

(Not Supplied)

EOL Resistor

from FACP

Digital Communicator or

Local

Annunciator Dr

y

output Contact

(Form "C" contacts)

These circuits are used to monitor
AC and Bat Fail and will cause a
simultaneous trouble condition
to the FACP's IN1 and IN2
(Non-Supervised)

Factory Installed

Board Interface

Cable

AC

Fuse

Cover

unswitched 115VAC

50/60Hz, 4.4 amp

power mains

(non power-limited)

Magnetic

Door Holder