- 6 -

AL642ULADA

Note: Unit is equipped with two (2) 1 amp max. auxiliary outputs: “AUX1” will automatically disconnect when
AC is lost. “AUX2” will remain battery backed up during power outage. For loads connected to “AUX2” please,
refer to battery “Stand-by Specifications” pg. 3 for ratings. When loads are connected to the “AUX1” and or
“AUX2” outputs during alarm condition, the remaining outputs may, not exceed 6.5 amp total alarm current.
(example: AUX1 = 1 amp, AUX2 = 1 amp, outputs up to 6.5 amp).

Terminal Identification Table:

AL600ADA - Power Supply Board

Terminal Legend Function/Description
L, G, N

Connect 120VAC to these terminals: L to hot, N to neutral.

- DC +

24VDC @ 6.5 amp in alarm non-power limited output.

AC FAIL
NO, C, NC

Form “C” dry contacts indicate the loss of AC, with AC present terminals marked [NO and C]
are open, [NC and C] are closed. When loss of AC occurs terminals marked [NO and C] are
closed, [NC and C] are open.

AC LOCAL
NC, NO, C

Form “C” dry contacts used to instantaneously signal the loss AC to local annunciation devices,
with AC present terminals marked [NO and C] are open, [NC and C] are closed. When loss of AC
occurs terminals marked [NO and C] are closed, [NC and C] are open.

BAT FAIL
NO, C, NC

Form “C” dry contacts indicate low battery voltage or loss of battery voltage. Under normal
conditions terminals marked [N.O. and C] are open, [NC and C] are closed. During a trouble
condition terminals marked [N.O. and C] are closed, and [N.C. and C] are open (Fig. 2, pg. 7).

+ BAT -

Stand-by battery input (leads provided) (Fig. 2, pg. 7).

*Power Board Parameter Specifications:

• AC Fail condition will report approximately 30 seconds after loss of AC. To delay report for 2.5 to 3 hours cut

jumper AC DELAY on the Power Supply Board (AC trouble output delay option). If this mode is selected the Power

Supply Board must be reset by removing all power to it for 30 seconds.

• Low battery condition will report at approximately 21VDC.

• Battery presence detection will report with in 180 seconds after battery remains undetected (missing or removed).

A restored battery will report within 30 seconds.

LED Diagnostics:

AL600ADA - Power Supply Board

Red (DC)

Green (AC) Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC, Stand-by battery supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

AL842LGK - Logic Board

LED

OFF

ON

BLINK (LONG)*

BLINK (SHORT)**

ON

Normal

Alarm Condition

Trouble Condition

Trouble Condition Memory

ON

Normal

Alarm Condition

Trouble Condition

Trouble Condition Memory

OFF

Normal

Alarm Condition

Trouble Condition

Trouble Condition Memory

OFF

Normal

Alarm Condition

Trouble Condition

Trouble Condition Memory

Input 1

Normal

Alarm Condition

Trouble Condition

---

Input 2

Normal

Alarm Condition

Trouble Condition

---

Fault

Normal

Alarm Condition

---

---